The TR selection uses tons of refrigeration as a cooling-capacity rate.

Measurement basis

The reference convention is US 12,000 BTU IT/h, equal to the stored watt factor per refrigeration ton.

Definition conventions

Horsepower is mechanical unless marked metric. PS equals metric horsepower. Refrigeration tons use the US 12,000 BTU IT/h convention.

Conversion method

Use the stored TR power ratio to read watts or another power unit, keeping the International Table BTU convention.

Reference equivalent of TR

1 TR = approximately 3516.85284207 W.

Recorded scale factors: 3516.852842066667 for TR; 1 for W.

Worked example

Known input: 10 TR. Reference equivalent: 35168.5284207 W. The return conversion gives approximately 10 TR.

The reference example is a cooling-capacity comparison rather than a ton-mass conversion.

Common reference values

Input (TR)Reference equivalent (W)
13516.85284207
517584.2642103
1035168.5284207
2587921.3210517
50175842.642103
100351685.284207

Compare one TR with other units

Target unitEquivalent of 1 TRDefinition guide
Watts (W)3516.85284207Read definition
Kilowatts (kW)3.51685284207Read definition
Megawatts (MW)0.00351685284207Read definition
btu per hour (BTU IT/h)12000Read definition
Mechanical horsepower (hp mech)4.71617734707Read definition
metric horsepower (hp metric)4.78158914895Read definition
Nanowatts (nW)3516852842070Read definition
Microwatts (µW)3516852842.07Read definition

What a ton of refrigeration measures

A ton of refrigeration, abbreviated TR, is a unit of cooling power, which means a rate of heat removal. The word ton here has nothing to do with weight. Under the US convention used on this page, one TR equals 12,000 BTU per hour, with the BTU taken as the International Table BTU. That is 200 BTU per minute. The unit is the standard way to rate air conditioners, heat pumps in cooling mode and chillers in the United States, so a three-ton residential unit is a system rated at 36,000 BTU/h of cooling. It describes the heat the equipment can remove under stated test conditions, not the electricity it draws. Electrical input is a separate number, and the ratio of the two is the efficiency.

Origin in melting ice

The ton of refrigeration comes from the era when ice was the standard cooling medium. It is the rate of heat absorption needed to melt one short ton, 2,000 pounds, of ice at its melting point in 24 hours. The latent heat of fusion of water is about 144 BTU per pound in the older BTU-based convention, which is close to the modern value of roughly 334 kJ/kg. Multiplying 144 BTU/lb by 2,000 lb gives 288,000 BTU, and spreading that over 24 hours gives 12,000 BTU per hour. The definition survives as a fixed number even though ice is no longer how most cooling is delivered. This history explains why a refrigeration ton is tied to a short ton and why other regions using a metric tonne of ice got different values. It also shows that the unit is a rate: one TR continues to mean 12,000 BTU/h whether or not any ice is involved.

Exact conversion to watts

The International Table BTU equals 1,055.05585262 joules exactly, as given in NIST SP 811. One TR is 12,000 BTU per hour, so in watts it is 12,000 times 1,055.05585262 divided by 3,600, which is 3,516.8528421 W. In practical terms, 1 TR is about 3.517 kW. The other common conversions follow. One TR equals about 4.716 mechanical horsepower, using 745.7 W per horsepower, and about 3,024 kilocalories per hour using the International Table calorie. A system rated at 3 TR therefore removes about 10.55 kW of heat, and a 500 TR chiller about 1,758 kW. For quick work, many engineers use 3.5 kW per TR, which carries about a 0.5 percent error. When a specification will be audited, use the full factor, since rounding accumulates when ratings are added across many units in a central plant.

Sizing examples

Two illustrative cases show how the unit is used. A small commercial space has a calculated peak sensible and latent cooling load of 54,000 BTU/h. Dividing by 12,000 gives 4.5 TR, so the designer would look at equipment rated at five tons rather than four. In watts that load is 15.83 kW. For a larger plant, suppose a district cooling design calls for 1,200 TR. That is 1,200 times 3.5168528, or about 4,220 kW of cooling, and the heat rejected at the condenser will be larger because it includes the compressor work. A chiller rating is not the same as the load, because load calculations from ASHRAE methods involve occupancy, solar gain, ventilation and equipment heat. The TR figure appears only at the end, when the calculated load is matched to a piece of equipment. These numbers are illustrative and are not design recommendations.

Cooling output versus electrical input

A refrigeration ton is a measure of heat moved, so it cannot be compared directly with the kilowatts a compressor draws. Chiller efficiency is often stated in kW per TR, where lower is better, and well-designed water-cooled chillers are commonly described in the range of roughly 0.5 to 0.7 kW/TR at design conditions. The coefficient of performance, or COP, is the dimensionless ratio of cooling delivered to electrical input. Because 1 TR is 3.5169 kW of cooling, a chiller at 0.6 kW/TR has a COP of 3.5169 divided by 0.6, or about 5.86. For a 500 TR example at that figure, the compressor draws about 300 kW to remove 1,758 kW of heat, and the condenser must reject roughly 2,058 kW, the sum of the two. The numbers are an illustration of the arithmetic. Actual equipment performance depends on the model, load fraction and temperatures.

Rating conditions travel with the number

A capacity stated in TR holds for specific operating conditions. For unitary air conditioners and chillers, test standards such as those from AHRI specify entering air or water temperatures, humidity and flow rates. A unit rated at 3 TR under one set of conditions delivers less on a hot afternoon with a high condensing temperature and more when the outdoor air is cool. Water-cooled chiller ratings depend on the chilled-water supply temperature and the condenser water temperature. Because of this, comparing two nameplate tonnages is meaningful only if they were rated to the same standard conditions. Manufacturers publish performance tables that show capacity at other conditions, and those tables are the source for design work. A unit conversion only restates the rating in watts or BTU/h. It does not adjust the capacity for conditions, altitude, refrigerant or part load.

Other tons of refrigeration

The US value is not the only one in use. The Japanese refrigeration ton, written JRT, is defined from a metric tonne of ice and a latent heat of 79.68 kcal/kg, which gives 3,320 kcal/h, about 3.861 kW. Because data sheets from different regions may both write a plain TR, always look for the stated convention. The distinction can change a capacity by about 10 percent, which matters when equipment is sized close to its load. This page uses the US 12,000 BTU/h definition, which is 3.517 kW per TR. If a document lists a ton of refrigeration with kW equivalents next to it, compare the kW figure with the factor above to learn which convention the author used. A mismatch usually signals a different ton.

Not a weight, not a force, not a tonne

Three confusions come up often. The ton in TR is neither a short ton of mass nor a metric tonne, although the unit name inherits the word from the ice definition. A refrigeration ton is also not a ton-force, so it cannot be converted with gravity. And a ton of refrigeration is not a stored amount of cooling. Thermal storage systems do measure stored cooling energy, and the unit for that is ton-hour, which is one TR sustained for one hour, equal to 12,000 BTU or about 12.66 MJ. An ice storage tank described as holding 2,000 ton-hours stores about 24 million BTU of cooling. Mixing up TR with ton-hours is a rate versus quantity error similar to confusing kilowatts with kilowatt-hours. When a document gives only a number and the word ton, check the surrounding words and the dimensions before converting.

Practical notes on reporting

When writing a capacity in a specification or report, give the unit symbol, the convention and the conditions. A sentence such as 150 TR (527.5 kW) at the stated chilled-water and condenser-water temperatures is more useful than 150 tons. State the BTU convention if the document is used internationally, because the thermochemical BTU differs from the International Table BTU by a small fraction of a percent. Keep one decimal place for ratings above 100 TR and two for small units, and do not round before summing capacities of several machines. When converting the final result to kilowatts for an international audience, use 3.5169 kW per TR and show the TR value alongside, which lets a reader check it. Capacity reductions for altitude, fouling or glycol content are applied by the designer from manufacturer data and are not part of a unit conversion.

Water flow that carries a ton

The TR also links to water flow through the heat balance Q = 500 × gpm × ΔT, where Q is in BTU/h, flow is in US gallons per minute, ΔT is in °F and 500 is a rounded product of water density, specific heat and minutes per hour. Rearranging for one TR at a 10 °F chilled-water temperature rise gives 12,000 divided by 500 times 10, or 2.4 gpm per ton. A 500 TR chiller at that rise circulates 1,200 gpm. In SI, 3.5169 kW with a 5.56 K rise needs about 0.151 liters per second, since the specific heat of water is 4.186 kJ/(kg·K). The condenser side carries more heat, so cooling tower practice often uses a cooling tower ton of 15,000 BTU/h, which corresponds to 3 gpm at a 10 °F range. These pairs of numbers are standard design arithmetic, and they show why a TR figure always implies a water or air flow somewhere.

Heat pumps and the heating side

Heat pumps in the United States are sold with the same ton labels, and the tonnage refers to cooling capacity at rated conditions. A three-ton heat pump delivers 36,000 BTU/h of cooling, and its heating output at a mild outdoor temperature is stated separately in BTU/h or kW, often a similar or somewhat higher number, and it declines as outdoor temperature falls. The fact that the same machine has different capacities in the two modes is why the unit label alone does not tell you the heating output. When converting to kW, convert each rating separately with its own conditions. A 3 TR cooling rating is 10.55 kW. If the heating rating at a stated outdoor temperature is 34,000 BTU/h, it equals 9.96 kW. Both come from the same BTU factor, and neither can be inferred from the other.

Precision and checking

  • Retain source power precision.
  • Keep the US refrigeration convention.

Reference numbers are displayed with up to twelve significant digits. That display does not add precision to a rounded measurement. Keep source and target quantities compatible, confirm symbol case and regional conventions, and round the final result to precision justified by the input. Factors involving π or repeating fractions use finite numerical precision.

Use a working converter

Source and verification scope

The reference values and examples use the versioned unit definitions shared with the linked converters. Source dates identify the stated access or verification scope. A reverse calculation checks arithmetic and direction, but it does not independently verify a definition. Computandum is independent of the cited organizations, and the citations do not imply endorsement of this guide or a real application.