Putting a ton on the same scale as a light bulb

The watt is the SI unit of power, and expressing a cooling capacity in watts lets you compare it with every other load in a building: lamps, computers, heaters, pumps. This page converts tons of refrigeration to watts using W = TR × 3,516.85284207. The default input of 10 TR gives 35,168.52842066667 W, about 35.2 kW. Besides watts the lists include kilowatts, megawatts, nanowatts, microwatts, milliwatts, gigawatts, BTU per hour and both horsepower units, so any of them is a selection away. The result is a rate of heat removal. A 10 ton air conditioner removes heat at the same rate that a 35 kW electric heater adds it.

The BTU definition

The ton is defined as 12,000 BTU(IT) per hour, equivalently 200 BTU per minute. A BTU, the British thermal unit, is a unit of energy. The international table BTU is exactly 1,055.05585262 J, derived from the international table calorie, and a watt is a joule per second. So 12,000 BTU per hour is 12,000 × 1,055.05585262 / 3,600 = 3,516.8528421 W, which is where the factor comes from. The page prints the product of the factor and the input with full precision, so 10 TR gives 35,168.52842066667 W. For comparison, 1 BTU/h is 0.29307107 W. A rule of thumb that follows is that 1 ton is about 3.5 kW and 1 kW is about 3,412 BTU/h. Both rules are close enough to estimate in your head, and the page supplies the exact figure.

The ice story in SI terms

The ton is named for the cooling effect of melting a ton of ice. A short ton is 2,000 lb, or 907.18474 kg. The latent heat of fusion of ice is about 144 BTU per pound, which is 334.9 kJ per kilogram, and the real value for pure water ice is about 334 kJ/kg. Melting a short ton absorbs 907.18474 × 334.944 kJ, which is about 303.9 MJ. Spread over 24 hours (86,400 s), that is 303,855 kJ / 86,400 s = 3.5169 kW. The agreement with the BTU definition is by construction, since 144 BTU/lb was used to define the unit. The story is useful for intuition. One ton of cooling is the heat flow that would melt a short ton of ice in a day, which is why the unit carries the name of a mass.

Worked examples

Start with the common residential size. A 3 ton air conditioner has a nominal capacity of 3 × 3,516.8528 = 10,550.56 W, or 36,000 BTU/h. A half-ton window unit is 1,758.43 W. A large commercial chiller of 150 TR is 527,527.93 W, which is 527.5 kW. In the other direction, suppose a datasheet lists a cooling coil at 7,000 W and you want tons. Divide 7,000 by 3,516.85 and the answer is 1.99 TR, which a US contractor would call a 2 ton coil. Another quick estimate: a room with 2,500 W of equipment load needs 0.71 TR of cooling for that load alone, since 2,500 / 3,516.85 = 0.711. These figures are illustrative round numbers and show the page's arithmetic. Actual cooling loads include people, lighting, solar gain and ventilation.

Comparing with electric heaters

It is instructive to compare a ton with common appliances. A portable space heater draws about 1,500 W, so a single ton of cooling capacity, at 3,517 W, matches the heat output of 2.3 such heaters. A 10 ton system at 35,169 W matches about 23 of them running at once. The comparison helps explain why a seemingly small number of tons carries a large load on a building. It also explains why air conditioning dominates the electric demand of many buildings on hot days, even though the compressor input is much smaller than the cooling. The compressor input is a fraction of the cooling because the machine moves heat instead of making it. When you compare a cooling capacity in watts with the power input in watts, keep the two labeled apart.

Watts per ton, EER and COP

Efficiency ratings tie the two watt figures together. The coefficient of performance is cooling watts divided by electrical watts, and it is dimensionless. The energy efficiency ratio is BTU/h of cooling divided by watts of input. Because 1 W is 3.41214 BTU/h, EER equals COP times 3.41214. A system with an EER of 12 has a COP of 3.517, and it uses 12,000 / 12 = 1,000 W of electricity per ton of cooling. Raising the EER to 15 cuts the input to 800 W per ton. Chiller plants often use kW per ton, so 0.6 kW/ton equals a COP of 5.86. The converter on this page gives the numerator of these ratios. If you have an EER and a tonnage, the electrical input in watts is 12,000 × tons / EER.

Latent and sensible cooling

A ton rating covers the total heat removal, which includes sensible cooling that lowers the air temperature and latent cooling that condenses moisture from the air. In a humid climate a large share of the load can be latent, and equipment is chosen with a sensible heat ratio that matches. When a coil is listed with a total capacity of 7,000 W and a sensible capacity of 5,300 W, the latent part is 1,700 W, and the sensible heat ratio is 0.76. The converter works equally well on any of the three figures, because each is a rate of heat flow in watts. What it does not do is decide which of them matters for your design. A unit with the right total capacity but a poor sensible ratio can leave a space cold and clammy.

BTU variations and accuracy

The international table BTU used for the ton is not the only BTU. The thermochemical BTU is 1,054.35 J, the 39 °F BTU is about 1,059.67 J and the 59 °F BTU is about 1,054.80 J. Using one of the others changes the ton by well under one percent, with the thermochemical choice giving 3,514.5 W. Standards in the HVAC industry use the international table BTU, as does this page. In practice, the uncertainty of a field capacity measurement is several percent, so the BTU variants rarely matter. What can matter is the rounding in a data sheet: a ton quoted as 3.5 kW and another as 3.517 kW differ by 0.5 percent. For a 150 TR plant, that difference is about 2.5 kW, a number to watch when you reconcile quotes from different suppliers.

Rounding the result

The page prints sixteen digits for 10 TR, which is far more than any real capacity justifies. For reporting, keep as many significant digits as the input. A nominal 10 TR unit is a two-digit number, and 35 kW or 35,200 W is the appropriate answer. Quoting 35,168.528 W implies knowledge of the capacity to the milliwatt. If you have a measured capacity, such as 9.6 TR at the test conditions, use that number in the converter and round the result to three digits, which is 33,800 W. Chains of conversions should be avoided. If you need BTU/h, ask the page for BTU/h directly, not for watts followed by a hand conversion with a rounded constant.

What the conversion leaves out

The page converts a rate of heat flow from one unit to another. It does not calculate installation limits, equipment ratings, protection, material response or compliance, and it does not size electrical supplies, piping, ducts or refrigerant charge. The watts it returns are thermal watts of cooling, not the electrical watts that a machine draws. A cooling load calculation, a manufacturer's capacity table and the governing codes are the proper sources for design decisions. Use this page for what it does well, which is turning a ton figure into watts or the other way round without mistakes in the long constant.

Reference values in watts

A short list of tonnages helps with estimation. One ton is 3,516.85 W. Two tons are 7,033.71 W, five tons 17,584.26 W, twenty tons 70,337.06 W, fifty tons 175,842.64 W and one hundred tons 351,685.28 W. The relation is linear, so any tonnage scales from these. A thousand-ton district cooling plant removes heat at 3.517 MW. Fractions work as well: a quarter ton is 879 W, about the heat of a desktop computer with a monitor. These values are exact multiples of the factor, rounded for display. They make a handy reference when a document gives watts and you want a sense of size. If the watt figure is close to a multiple of 3,517, the unit is probably a nominal ton rating, and a figure far from any such multiple may be a measured value at specific conditions.

Airflow per ton

Air systems tie watts of cooling to airflow. A common rule of thumb is about 400 cubic feet per minute of air per ton of cooling, with typical figures between 350 and 450. The sensible heat carried by air follows Q = 1.08 × CFM × ΔT in BTU/h with ΔT in degrees F. For 400 CFM cooled by 20 °F, that is 8,640 BTU/h, which is 2,532 W. The total for one ton is 3,517 W, so the remaining 985 W is latent cooling that removes moisture, giving a sensible heat ratio of 0.72. Systems that move too little air per ton freeze the coil, and systems that move too much leave humidity high. These numbers are illustrative rules of thumb and not design values. The page supplies the total in watts, and the airflow and split between sensible and latent come from the design conditions.