btu per hour (BTU IT/h): power unit guide

BTU IT/h describes an energy-transfer rate.

Measurement basis

The stored watt factor is approximately 0.2930710701722222.

Definition conventions

Horsepower is mechanical unless marked metric. PS equals metric horsepower. Refrigeration tons use the US 12,000 BTU IT/h convention.

Conversion method

Use the recorded power ratio, retaining both the International Table energy convention and hourly denominator.

Reference equivalent of BTU IT/h

1 BTU IT/h = approximately 0.293071070172 W.

Recorded scale factors: 0.2930710701722222 for BTU IT/h; 1 for W.

Worked example

Known input: 10 BTU IT/h. Reference equivalent: 2.93071070172 W. The return conversion gives approximately 10 BTU IT/h.

The worked rate remains power rather than a plain BTU energy amount.

Common reference values

Input (BTU IT/h)Reference equivalent (W)
10.293071070172
51.46535535086
102.93071070172
257.32677675431
5014.6535535086
10029.3071070172

Compare one BTU IT/h with other units

Target unitEquivalent of 1 BTU IT/hDefinition guide
Watts (W)0.293071070172Read definition
Kilowatts (kW)0.000293071070172Read definition
Megawatts (MW)2.93071070172e-7Read definition
Mechanical horsepower (hp mech)0.000393014778922Read definition
metric horsepower (hp metric)0.000398465762413Read definition
tons of refrigeration (TR)0.0000833333333333Read definition
Nanowatts (nW)293071070.172Read definition
Microwatts (µW)293071.070172Read definition

A rate of heat flow quoted on American equipment

One BTU IT per hour is a power, the rate at which energy flows. In practice it is the standard rating unit for American furnaces, boilers, water heaters, window air conditioners and baseboard heaters. The number on a nameplate such as 80,000 BTU/h tells you how quickly the machine can deliver heat, not how much heat it stores. The unit combines the international-table BTU, an energy of 1,055.05585262 joules, with the hour, which is 3,600 seconds. That makes 1 BTU IT/h = 1,055.05585262 / 3,600 W, or about 0.293071 W. A rated heater and a stored amount of heat should never share a column, because they carry different dimensions even though both use the letters BTU.

The factors the converter uses

Converting to SI is a matter of one multiplier. Watts equal BTU IT/h × 0.293071070172, kilowatts equal BTU IT/h × 0.000293071070172, and in reverse BTU IT/h = W × 3.41214163313. A 1 kW electric heater therefore delivers 3,412.14 BTU/h, and a 1,500 W space heater delivers 5,118.2 BTU/h (1.5 × 3,412.14). An 80,000 BTU/h furnace input equals about 23.45 kW. A 5,000 BTU/h window air conditioner moves heat at about 1,465 W. Against mechanical horsepower, 1 hp is 2,544.43 BTU IT/h, so a 1 hp motor running at full output is about 2.54 MBH. These factors are fixed by the BTU definition, not measured, so they carry the number of digits you choose to keep.

Why a ton of cooling is 12,000 BTU per hour

Cooling capacity is still sold in tons in the United States. One ton of refrigeration is defined as 12,000 BTU/h, which equals about 3.517 kW. The name comes from the rate at which a ton of ice, melting over 24 hours, absorbs heat: a short ton of ice at about 144 BTU per pound gives 288,000 BTU per day, and 288,000 divided by 24 is 12,000. A 3-ton residential air conditioner is thus rated at 36,000 BTU/h, about 10.55 kW of heat removal. The converter lists tons of refrigeration beside BTU per hour for this reason. Rated capacity is not the electrical power drawn, because a cooling machine moves more heat than the electric energy it consumes.

Input, output and efficiency

A nameplate may show input rating, output rating or both. A furnace rated at 80,000 BTU/h input and 80 percent efficient delivers about 64,000 BTU/h to the air, which is about 18.76 kW. The unit does not tell you which one a number refers to, so read the label rather than assuming. Electric resistance heaters are close to 100 percent efficient at the point of use, so 1 kW in is about 3,412 BTU/h out. Heat pumps deliver more heat than the electricity they use, which is why their ratings are given as capacity and a separate coefficient of performance. A calculation that compares equipment should use the same basis for each machine, with each value converted to the same unit before ranking them.

From a heat rate to energy and fuel

To find energy over time, multiply the rate by hours. A 5,000 BTU/h heater running for 3 hours delivers 15,000 BTU, which is 4.396 kWh or 15.83 MJ. For fuel planning, remember that a BTU of heat is not a BTU of fuel when the appliance is inefficient. If a boiler is 85 percent efficient and the building needs 40,000 BTU/h of heat, the fuel input must be 40,000 / 0.85, about 47,059 BTU/h. Utilities in the United States sell natural gas by the therm, which is 100,000 BTU, so that input uses about 0.47 therm per hour. These steps show why a rate unit and an energy unit are kept as separate converter families, with different groupings.

MBH, MMBH and the Roman numeral M

Industry shorthand adds to the confusion. MBH means thousand BTU per hour, because M stands for the Roman numeral for one thousand. MMBH or MMBTU/h means million BTU per hour. In the SI system, M means mega, one million, so the letter flips meaning between systems. A boiler listed as 500 MBH is 500,000 BTU/h, about 146.5 kW, not 500 million. When copying a value from a spec sheet, expand the abbreviation before you convert and write the number out in full. The converter here accepts BTU IT/h and does not interpret MBH, which means the multiplier by 1,000 has to be applied before entering the value. Doing so prevents a thousand-fold slip.

What a per-hour label prevents confusing

Energy and power share the BTU name, and a lost denominator turns a power into an energy. A statement that a house needs 30,000 BTU is ambiguous: per hour, per day, or per season. Heating load calculations produce a rate at a design condition, such as 30,000 BTU/h at an outdoor temperature of 5 °F, and annual energy estimates are separate figures in millions of BTU. Preserving the per hour in the source measurement lets you apply the right conversion group, from BTU IT/h to watts, instead of energy from BTU to joules. The two have different factors, 0.293071 against 1,055.056, and mixing them is an error by a factor of 3,600.

The IT mark and the reference BTU

The IT in the label identifies the international-table BTU. The thermochemical BTU is 1,054.350 J, which is 0.07 percent smaller, and older definitions tied to specific water temperatures differ by up to roughly half a percent from the IT value. Most equipment ratings do not specify the definition and the difference is lost within test tolerance, but a conversion table should still state which one it uses. This site follows the IT convention and lists it in the unit symbol. Nominal ratings are also measured at stated test conditions, for example specified indoor and outdoor air temperatures for air conditioners, so two machines with the same BTU/h rating can behave differently in a real room.

Sizing a heater from a room load

As an illustration, suppose a heat-loss estimate for a small addition gives 18,000 BTU/h at the design outdoor temperature. Converted, that is 18,000 × 0.293071 = 5,275 W, so a 5 kW electric heater would fall slightly short and a 6 kW unit would cover it. A gas unit with 90 percent efficiency would need 18,000 / 0.9 = 20,000 BTU/h of input. Matching units before comparing prevents the most common sizing slip, which is comparing a wattage on one box with a BTU rating on another. The heat-loss number itself comes from areas, insulation and temperature differences, and is a separate calculation from this unit conversion.

Precision and checking

  • Keep source rate precision.
  • Retain IT/h on the label.

Reference numbers are displayed with up to twelve significant digits. That display does not add precision to a rounded measurement. Keep source and target quantities compatible, confirm symbol case and regional conventions, and round the final result to precision justified by the input. Factors involving π or repeating fractions use finite numerical precision.

Use a working converter

Source and verification scope

The reference values and examples use the versioned unit definitions shared with the linked converters. Source dates identify the stated access or verification scope. A reverse calculation checks arithmetic and direction, but it does not independently verify a definition. Computandum is independent of the cited organizations, and the citations do not imply endorsement of this guide or a real application.

Sources

Read the calculation and sourcing methodology →