A bridge between two sets of catalogs
Cooling equipment is sold by the ton, and engines, pumps and motors in many regions are sold by metric horsepower. A project that mixes the two, such as an engine-driven chiller, a refrigerated ship or a plant with diesel standby drives, may need both in one table. This page converts tons of refrigeration (TR) into metric horsepower. With the factor 4.78158914895, the default input of 10 TR becomes 47.81589148950514 hp metric. The lists also include watts, kilowatts, megawatts, BTU per hour, mechanical horsepower and PS, so other routes are one selection away. Be clear about what the result means. It states the heat flow of a cooling capacity in the unit of horsepower. It does not state how much engine or motor power it takes to deliver that cooling, which is a separate and smaller figure for any refrigeration cycle that works.
Building the factor
The factor is a ratio of two exact definitions. A ton of refrigeration is 12,000 BTU(IT) per hour, and with 1 BTU(IT) = 1,055.05585262 J this equals 3,516.8528421 W. A metric horsepower is 75 kgf·m/s, equal to 735.49875 W at standard gravity. Dividing, 3,516.8528421 / 735.49875 = 4.78158914895. Ten tons then gives 47.8158914895 hp metric, and one ton gives 4.7816. The page prints this as 47.81589148950514, using the full double-precision result. The reverse factor is 0.2091355 TR per hp metric, so a 25 PS value is 5.228 TR. Since PS and hp metric are equal in this converter, the same factor applies to the PS entries in the lists, and a ton is a little under 4.8 metric horsepower in whichever name you prefer.
Cooling capacity is not shaft power
The distinction matters most in practice. A refrigeration machine moves heat from cold to warm using work, and the cooling delivered is a multiple of the work put in. That multiple is the coefficient of performance. A water-cooled chiller might use 0.6 kW of electrical input for each ton of cooling, equal to a COP near 5.9. Per ton, 0.6 kW is 0.6 / 0.73549875 = 0.816 hp metric of input power, which is about one sixth of the 4.78 hp metric that the cooling capacity corresponds to. So a 10 TR chiller whose cooling equals 47.8 hp metric would need about 6 kW or 8.2 hp metric at the compressor in this illustrative case. Reading a 47.8 hp figure as a motor size would overestimate the drive by a factor of about six. The power-to-power conversion is the right tool for comparing units on paper, and the compressor input needs its own rating.
Engine-driven and absorption systems
Some refrigeration plants do not run on electricity. Engine-driven chillers use a gas or diesel engine on the compressor shaft, and absorption chillers use heat rather than mechanical work. Engine-driven units can be rated by the engine's power in horsepower and the cooling in tons. For these systems the page can help relate the two ratings, with the reminder that the cooling is a multiple of the shaft power. An engine delivering 100 PS to a compressor with a COP of 4 would yield 400 PS-equivalents of cooling, which is 84 TR, since 400 / 4.78159 = 83.65. The same compressor at a lower COP in hot weather delivers less. These are illustrative numbers and they leave out the engine heat recovery that many installations use. Check the manufacturer's performance curves for real values.
A worked example with a larger plant
Take a 150 TR chiller plant on a hospital campus. The conversion is 150 × 4.78158914895 = 717.2384 hp metric, or about 527.5 kW of cooling, since 150 × 3.5168528 = 527.53 kW. If the chiller performs at 0.65 kW per ton, the electrical input is 97.5 kW, which is 132.6 hp metric. The comparison between 717 hp metric of cooling and 133 hp metric of input highlights the heat-pump effect. A second example goes the other way: a document lists a 60 PS engine and asks what cooling load that power would match if it were converted one-to-one. Dividing 60 by 4.78159 gives 12.55 TR. Again, that is a unit identity, not a performance claim. Both examples use illustrative figures and do not describe a particular machine.
Where tons and PS appear together
It is common in international projects to meet tons on the air-conditioning side and PS or hp on the drive side. In India, the Middle East and parts of Southeast Asia, air conditioners and chillers are sold in TR, while pumps and engines may come with PS or hp ratings from European or Japanese suppliers. A tender for a cold storage facility might list compressors by input kW, evaporators by cooling kW or TR, and a diesel genset by kVA. Converting everything to kilowatts or to a single horsepower makes a table coherent. The page supports either approach. For tonnage, one TR is 3.517 kW, and for drive power one PS is 0.7355 kW. A quick check on any pair is that the ratio of the two kW figures should be 4.78, so a number far from that ratio signals a mislabeled unit.
Ratings, conditions and efficiency labels
Cooling capacity depends on the conditions at which it is rated. Manufacturers state it at defined water or air temperatures, and capacity falls when the condenser is warmer. Efficiency is reported as kW per ton, COP, EER or integrated part-load values, and each describes the relationship between cooling and input in a different way. The IPLV, for instance, weights performance at several load levels. None of those quantities can be recovered from the tons-to-horsepower factor. A converter between two capacities is a one-line calculation, and a performance comparison needs the full data. If you are given only a tonnage, you can compare size, and if you also want to compare running cost, ask for the efficiency at the operating conditions.
Rounding and number of digits
The factor is exact to the digits shown, but the tonnage on a nameplate is a nominal value. A 10 TR unit may deliver 9.6 TR at actual conditions, and manufacturer ratings are typically allowed a small tolerance. Presenting the conversion as 47.8 hp metric, with three significant figures, is enough. If you convert several rows of a table, keep the same number of significant digits in all of them, and note the basis, for example TR at standard rating conditions. Avoid rounding the factor itself. Using 4.78 instead of 4.78159 gives a 0.03 percent error, which is tiny, but errors from rounding in chained conversions tend to accumulate, so use the page to convert directly between the two units you need.
Limits of the page
The page converts one power unit into another. It assumes the entered value is a rate of heat removal expressed in tons of refrigeration and does not compute the shaft power needed to deliver it. It does not calculate installation limits, equipment ratings, protection, material response or compliance, and it does not size compressors, motors, engines or electrical supplies. For those tasks use the manufacturer data, a load calculation and the relevant codes. Use the result to relate documents written in different units, and keep the labels with the numbers so that the cooling capacity is never mistaken for the input power of the machine.
Cross-checking through BTU per hour
A third route to the same factor goes through BTU per hour, which the lists include. One metric horsepower of 735.49875 W equals about 2,509.6 BTU(IT)/h, since 1 W is 3.41214 BTU/h. One ton is 12,000 BTU/h. Dividing, 12,000 / 2,509.6 gives 4.7816, matching the page. This is a good habit when you suspect a factor in a document. Take the ton as 12,000 BTU/h, the metric horsepower as about 2,510 BTU/h, and divide to see if the result is near 4.78. A reading of 4.0 or 5.0 would suggest a different definition of the ton, such as the Japanese refrigeration ton of about 3.86 kW, or of the horsepower. In that case the listed units on the page do not apply, and you must convert from the unit that the source actually used.
Pumps and fans for the same plant
The auxiliary equipment of a refrigeration plant is often specified in horsepower even when the plant is specified in tons. A 150 TR chiller at 2.4 gpm per ton circulates 360 gpm of chilled water. At 60 ft of pump head, the water horsepower is 360 × 60 / 3,960 = 5.45 hp, using the standard constant 3,960 for gpm and feet. If the pump runs at 70 percent efficiency, the shaft needs 7.79 hp mech, which is 7.90 hp metric. This pump power is small next to the 717 hp metric that the cooling capacity represents, and also small next to the compressor input. The example shows why one converter number should not be read as the size of any one motor. Each machine in the plant has its own duty and efficiency, and the tons figure only gives the cooling duty.
Reverse conversions
The reverse direction answers questions such as how much cooling a given amount of mechanical power would represent as a heat flow. Divide metric horsepower by 4.78159 to get tons. A 100 PS machine, which is 73.55 kW, corresponds to 20.91 TR of heat flow. A 25 hp metric value corresponds to 5.228 TR, and 60 hp metric to 12.55 TR. These numbers are mainly useful for orders of magnitude, for example when someone says a small cold room needs a 10 hp compressor and you want to see what cooling that implies. The real answer depends on the refrigerant, the evaporating and condensing temperatures and the type of compressor, so refer to compressor performance tables for actual selections.