Two ends of the resistance scale
Electrical technicians meet megaohms and microohms in different jobs. Megaohms describe insulation: a healthy cable or motor winding should resist leakage current with millions of ohms. Microohms describe the opposite, the tiny resistance of a bolted joint, a circuit-breaker contact or a busbar splice, where a few tens of microohms can mean the difference between a cool connection and a hot one. A conversion across all twelve orders of magnitude is rarely needed in one task. It does appear in training material, in software that works in a single fixed unit and in tables that cover the whole range. This page multiplies by 10 to the twelfth. The default 10 MΩ returns 10,000,000,000,000 µΩ. It reports the unit change only and does not interpret the reading as good or bad.
The factor of 10 to the 12th
The prefix mega is 10 to the sixth and micro is 10 to the minus sixth, so one megaohm is 10 to the sixth ohms, which is 10 to the twelfth microohms. The formula is µΩ = MΩ × 1e12. The ohm is the SI derived unit of electrical resistance, defined as one volt per ampere, and its prefixes are listed in the BIPM SI Brochure. The reverse direction divides by 1e12: 150 µΩ is 1.5e-10 MΩ. A two-step check helps: 10 MΩ is 10,000,000 Ω, and multiplying by 1,000,000 gives 10,000,000,000,000 µΩ. Counting zeros in a twelve-digit result is error-prone, so exponent notation is the practical way to write and verify it. The factor is exact, so any rounding comes only from the display.
Insulation resistance and the megohmmeter
Insulation testers, often called meggers after a trade name, apply a test voltage such as 500 V or 1,000 V DC to a cable or winding and read the resulting resistance, typically in megaohms or gigaohms. A common rule of thumb for low-voltage equipment is that readings should be at least in the megaohm range, and trending the readings over time is more informative than any single number. IEEE Std 43 and similar standards give recommended minimum values and test procedures for rotating machines, and the right threshold depends on the voltage rating and condition. The converter can express a 2.2 MΩ reading as 2,200,000,000,000 µΩ, but no technician would do so. The conversion helps only when a table or tool needs the value in microohms. Because insulation readings change with humidity and surface contamination, a reading taken on a damp day can be far lower than on a dry one, and the trend over several tests is more informative than one value.
Contact resistance in microohms
Micro-ohmmeters inject a high direct current, commonly 10 A to 200 A, and measure the small voltage drop across a joint or contact to find resistance in microohms. Using a four-wire (Kelvin) connection removes the resistance of the test leads. A breaker contact might read 30 to 100 µΩ, depending on its rating, and a manufacturer's data gives the acceptable limit. A reading that is much higher than similar joints suggests a loose bolt, a contaminated surface or damaged plating. As a simple illustration, a reading of 150 µΩ at 100 A dissipates 100² × 150e-6 = 1.5 W in the joint. The conversion to megaohms, 1.5e-10 MΩ, is only a unit exercise. The comparison against acceptance limits belongs in the equipment documentation. Similarly, a joint at 40 µΩ carrying 1,000 A dissipates 40 W, since 1,000² × 40e-6 equals 40, which shows why even small resistance increases matter at high current.
A worked example
A spreadsheet logs resistance in microohms for a maintenance database, and a technician types an insulation reading of 2.2 MΩ. The correct entry is 2.2 × 1e12, which is 2,200,000,000,000 µΩ. A reading of 0.5 MΩ, equal to 500 kΩ, becomes 500,000,000,000 µΩ. If the database field has a limit of about 1e9, these values would overflow. The better practice is to store each measurement in the unit the instrument displays and record the unit in a separate field. These numbers are illustrative. The example shows why a fixed-unit system for such a wide range is awkward, and why converters like this one exist. It also shows how easily a zero can go missing in a manual conversion of a twelve-digit result. Reversing the entry, 500,000,000,000 µΩ divided by 1e12 returns 0.5 MΩ, so a round trip is a quick way to confirm that the unit menus were set correctly before the number is saved in a record.
Oscilloscope and meter input resistances
Test equipment quotes input resistance in megaohms. A standard oscilloscope input is 1 MΩ, often with about 15 pF in parallel, and a typical digital multimeter has a 10 MΩ input on its voltage ranges. Converted, 10 MΩ is 1e13 µΩ, the default of this page. These inputs matter when measuring high-impedance circuits, because a meter with 10 MΩ input connected across a 10 MΩ source divides the voltage in half. A 10x probe raises the effective input to 10 MΩ and reduces loading. The converter does not model loading, and the example is a reminder that a resistance expressed in megaohms interacts with the circuit being measured. The value of the conversion is only unit consistency in documentation and software. A 1 MΩ oscilloscope input across a 1 MΩ source halves the signal in the same way.
Resistivity and why the numbers are so far apart
The range of resistance across materials is huge. Copper has a resistivity of about 1.7e-8 ohm meters, so a copper bar 1 meter long with a cross-section of 1 square centimeter has a resistance of about 170 µΩ. Common insulating plastics and ceramics have resistivities of 1e12 ohm meters or more, so a cube of such material measures far into the gigaohms. The twelve orders of magnitude between megaohms and microohms are small compared with the roughly 25 orders of magnitude between metals and the best insulators. These are approximate textbook values for pure materials at room temperature. Real components depend on shape, temperature and surface condition. The page converts a resistance value and does not derive it from material properties.
Temperature and test conditions
Resistance readings depend on temperature, test voltage and duration. Insulation resistance typically falls as temperature rises, and a common rule of thumb says it halves for every 10 degrees C increase, although the true behavior varies with the material. Readings are therefore corrected to a reference temperature, often 40 degrees C, before comparison with limits. The resistance of a copper conductor rises with temperature at roughly 0.4 percent per kelvin, which also shifts microohm readings. The converter does not correct for any of this. If you convert a reading to compare with an older record, make sure both were taken under similar conditions, and record the conditions together with the value. Otherwise the comparison may show a change that comes from the weather rather than the equipment.
Reporting and notation
Write the units as MΩ and µΩ, with a capital M and the Greek mu. If the characters are not available, spell out megaohm and microohm instead of using M and u, because plain-text abbreviations like Mohm and uohm are easily misread. In tables, choose one unit per column. Do not display twelve-digit numbers when exponent notation is clearer: 1.0e13 µΩ is easier to compare than 10,000,000,000,000. Keep the number of significant figures equal to the original reading. A megaohmmeter display of 2.2 MΩ has two significant figures, so 2.2e12 µΩ is the faithful report. Extra digits suggest a precision the instrument did not have.
Scope of the page
The page converts a resistance between prefixes of the ohm. It does not interpret readings, apply test standards, correct for temperature or judge whether insulation or a contact is acceptable. The factor is exact, so the result has the precision of the input. For maintenance and acceptance decisions, follow the equipment manufacturer's instructions and applicable standards, and use this page only for unit conversion.
Safe handling of the instruments
Insulation testers apply hundreds or thousands of volts, and micro-ohmmeters pass currents of tens of amperes or more, so the instruments need care. Equipment must be de-energized and verified dead before connection, and the stored charge in a cable or winding discharged after a test, because capacitance can hold a hazardous charge. Procedures come from the manufacturer and from standards such as those of the IEEE and the IEC, and from local safety rules. The conversion on this page has no bearing on safety. It only expresses a reading in another unit. Document the test voltage, duration, temperature and the instrument model with each reading, since those details make a number comparable with later tests and with the acceptance criteria.
Converting a whole log
A maintenance log often combines readings of very different size. Take a list: 4.7 MΩ for a cable, 0.85 MΩ for an older winding, 120 µΩ for a joint, 45 µΩ for a contact. Convert the two megaohm readings to microohms and they become 4.7e12 and 8.5e11. Then the four values can be sorted in one column, with the ratio between the largest and smallest readings, about 1e11 in this list. That ratio shows how different the two kinds of test are, and why they are not usually compared. The reverse conversion of the joint reading, 120 µΩ, gives 1.2e-10 MΩ. The values are invented to show the arithmetic. In practice, keep each kind of test in its natural unit and use conversion only where a tool requires it.