Thermal resistance values written in two systems
Thermal resistance describes how many degrees of temperature difference build up for each unit of heat flow. Large components such as water-cooled plates, power modules and industrial heat exchangers are often rated in kelvins per kilowatt, because their resistance per watt would be a tiny decimal. A design note, a vendor sheet or a US-based tool may instead ask for degrees Fahrenheit per watt. This page translates one into the other so the numbers can be used in the same calculation. It converts the unit only. The physical meaning stays the same: a temperature rise for each unit of power flowing through the path from the heat source to its surroundings.
Where the factor 0.0018 comes from
Two changes happen at once. The kilowatt in the denominator is 1,000 times larger than the watt, so a resistance of 1 K/kW equals 0.001 K/W. The temperature difference is then converted from kelvins to Fahrenheit degrees by multiplying by 1.8, because 5 K spans the same interval as 9 °F. Together, 0.001 × 1.8 gives 0.0018. No offset is added, since the quantity is a difference per unit of power and not a temperature reading. Reverse the conversion by dividing by 0.0018, so 0.018 °F/W equals 10 K/kW, and 1 °F/W equals about 555.56 K/kW. A value of 800 K/kW becomes 1.44 °F/W, and 5 K/kW becomes 0.009 °F/W. Because the factor is so small, results from kilowatt-scale values often land between 0.001 and 2, which is a useful range check. A result far outside it suggests a missed prefix on the input. Also confirm that the source says kilowatt and not watt, because a datasheet that lists K/W and a page that lists K/kW look alike at a glance, and the wrong choice shifts the answer by a factor of 1,000.
The opening example of 10 K/kW
The page starts with 10 K/kW. Multiplying by 0.0018 gives 0.018 °F/W. The value says that for each watt of heat passing through the path, the temperature difference grows by 0.018 °F, or 18 °F per kilowatt. That is a very low resistance, typical of a large cooling plate with good flow rather than a small finned heat sink. Checking it by steps gives the same result: 10 K/kW is 0.01 K/W, and 0.01 times 1.8 is 0.018 °F/W. If your output differs by a power of ten, the usual cause is mixing up the kilowatt and watt scales.
A cold plate carrying 3 kW
Suppose a water-cooled plate is listed at 40 K/kW and a converter stage dissipates 3 kW through it. The temperature rise across the plate is 40 × 3 = 120 K, which is 216 °F. In the other unit, 40 K/kW converts to 0.072 °F/W, and 3,000 W times 0.072 °F/W gives the same 216 °F. The two routes agree because the factors are consistent. This is the kind of check that catches errors when a design review passes numbers between a team using metric datasheets and a team working in US units. The illustrative figures are chosen only to show the arithmetic. A 5 K/kW path under the same load would give 15 K, or 27 °F.
Series paths add up
Heat usually passes through several layers, such as a semiconductor die, a baseplate, thermal paste and a cooler. Their thermal resistances add in series when expressed in the same unit. Converting each to °F/W before adding gives the same total as adding in K/kW and converting at the end. For example, resistances of 250 K/kW and 150 K/kW add to 400 K/kW, which is 0.72 °F/W. Converting the two parts separately gives 0.45 and 0.27, and their sum is again 0.72. Keep all parts in one unit before you add, and do not mix K/kW and °F/W entries in one sum.
Reading datasheet entries
Datasheets list thermal resistance with qualifiers such as junction to case or case to ambient, and the numbers describe a specific test setup. A value only applies when the mounting, airflow and contact surfaces match the sheet. The converter has no way to check this, so copy the qualifier along with the number. Where a sheet gives a transient thermal impedance curve instead of a single steady value, this page does not apply, because that quantity varies with pulse duration. Use the steady-state value for a constant load, and consult the manufacturer for pulsed loads or unusual mounting.
Thermal resistance and R-value are different quantities
Building insulation is rated by R-value, in units of °F·ft²·h/Btu, which is a thermal insulance for one square foot of material. Thermal resistance in K/kW or °F/W is for the whole object or path and does not include an area normalization. A converter between the two would need a surface area, and this page does not provide one. If you hold a wall assembly rating, do not enter it here. Use this page only for resistance values in K/kW and the neighboring per-watt units, such as kelvins per watt and degrees Celsius per watt.
Estimating a temperature rise in Fahrenheit
A US maintenance note may ask for the rise in degrees Fahrenheit for a given load. With a path of 120 K/kW and a load of 2 kW, the rise is 240 K, or 432 °F. In per-watt form, 120 K/kW is 0.216 °F/W, and 2,000 W times 0.216 gives the same 432. A rise that large would not occur in a working cooler, so the example shows why a real design needs low resistance and why the number is checked against a limit. The illustrative values are chosen to show the arithmetic. Add the rise to the ambient temperature in Fahrenheit, not to a Celsius value, or the result will be inconsistent.
Interval units and what is excluded
The degree Celsius per watt and the kelvin per watt carry the same numeric value, because a Celsius degree equals a kelvin. Fahrenheit degrees differ by the factor 1.8. The page treats the temperature part as an interval, so no offset such as 32 or 459.67 is used. The conversion does not predict a device temperature, since that needs the power, the ambient temperature and every resistance in the path. It does not check cooling adequacy or safety limits either. Results are shown to many decimals, and you can round to the precision of the datasheet value.