Measurement basis
Its reference factor is 5/9 K/W, stored with finite precision.
Definition conventions
These units express temperature difference per power. Building R-value uses area-normalized thermal insulance.
Conversion method
Multiply by 5/9 without an absolute-temperature offset.
Reference equivalent of °F/W
1 °F/W = approximately 0.555555555556 K/W.
Recorded scale factors: 0.55555555555555555555555555555555555555555555555556 for °F/W; 1 for K/W.
Worked example
Known input: 10 °F/W. Reference equivalent: 5.55555555556 K/W. The return conversion gives approximately 10 °F/W.
The example retains a temperature difference.
Common reference values
| Input (°F/W) | Reference equivalent (K/W) |
|---|---|
| 1 | 0.555555555556 |
| 5 | 2.77777777778 |
| 10 | 5.55555555556 |
| 25 | 13.8888888889 |
| 50 | 27.7777777778 |
| 100 | 55.5555555556 |
Compare one °F/W with other units
| Target unit | Equivalent of 1 °F/W | Definition guide |
|---|---|---|
| Kelvins per watt (K/W) | 0.555555555556 | Read definition |
| Kelvins per kilowatt (K/kW) | 555.555555556 | Read definition |
Temperature rise per watt of heat flow
Fahrenheit degrees per watt (°F/W) is a unit of thermal resistance. It states how many degrees of temperature difference are needed to push one watt of heat through a path, so a resistance of 2 °F/W means that a steady 10 W flow produces a 20 °F difference between the hot and cold ends. Thermal resistance is the thermal analogue of electrical resistance, with temperature difference playing the role of voltage and heat flow in watts playing the role of current. The SI unit is the kelvin per watt (K/W), and because a Fahrenheit degree is 5/9 of a kelvin, 1 °F/W equals 5/9 K/W, or about 0.5556 K/W, while 1 K/W equals 1.8 °F/W.
Why no 32-degree offset appears
Thermal resistance is built from a temperature difference, not from a temperature reading, so the offset between the Fahrenheit and Celsius scales cancels. That is the central difference from converting a thermometer reading. Converting 3 °F/W to K/W uses only the factor 5/9, giving 1.667 K/W. Since a Celsius degree and a kelvin are the same size, the value in °C/W is the same as in K/W, so 1.667 K/W is 1.667 °C/W. Applying the 32-degree offset to a resistance value produces a meaningless result. When a heat sink data sheet lists °C/W and a US document lists °F/W, multiply or divide by 1.8, and ignore the offset entirely.
Heat sinks and electronic cooling
The unit is most common in electronics cooling. A heat sink is described by the thermal resistance from the heat sink to ambient air, and a component data sheet adds a junction-to-case resistance. The total rise above ambient is the sum of the resistances in series times the power. A processor dissipating 65 W through a cooler of 0.3 K/W produces a rise of 19.5 K above the air entering it, which is 35.1 °F. The same cooler is rated at 0.54 °F/W. Because most data sheets use °C/W, the Fahrenheit form is mainly seen in North American thermal engineering notes and in older tables that grew from imperial units.
Worked example with power and rise
Take a power transistor dissipating 12 W with a combined thermal resistance of 4.5 °F/W from junction to ambient. The junction rises 12 × 4.5 = 54 °F above the surrounding air. If the ambient air is 77 °F, the junction runs at 131 °F, which is 55 °C. In SI terms, 4.5 °F/W is 2.5 K/W, and 12 W gives a 30 K rise, so the junction is 25 + 30 = 55 °C. The two routes agree. Note that the ambient temperature was added as a reading and the rise as a difference, which is the correct way to combine them. Keep the offset only for the final reading, never for the resistance.
Series and parallel thermal paths
Thermal resistances combine like electrical resistors. In series, they add: a chip with 1.0 °F/W to its case, a pad with 0.5 °F/W and a heat sink with 2.0 °F/W has a total of 3.5 °F/W. In parallel, reciprocals add, so two identical paths of 4 °F/W together behave like 2 °F/W. The approach assumes steady heat flow and fixed resistances, which is an idealization, since convection and radiation resistances change with temperature and airflow. Manufacturers therefore publish resistance at stated conditions, and a calculation with the nominal number holds only near those conditions.
Resistance versus R-value
Thermal resistance in °F/W applies to a whole object or path, and the building trade uses a related but different quantity, the R-value, which is resistance per unit area. US R-values have the unit ft²·°F·h/Btu, and 1 of those equals about 0.1761 K·m²/W. Converting between R-value and °F/W requires the area: a wall section of 100 ft² with R-13 has a total resistance of 13 / 100 = 0.13 °F·h/Btu, and the watt form needs the factor of 3.412 °F/W per °F·h/Btu, giving about 0.44 °F/W. The two quantities cannot be swapped without area, and mixing them is a frequent source of errors in insulation and electronics alike.
Cables, wires and housings
Thermal resistance also describes the path from a conductor or a motor winding to the air. A 1 m length of cable whose conductor-to-air resistance is 3 °F/W, for example, rises 30 °F above ambient when it dissipates 10 W. Ratings for current-carrying capacity, however, come from standards that include installation conditions and are not obtained from a converter. The conversion on this page restates the same resistance in a different unit and does not check any ampacity, safety or compliance question. For design decisions about heat, consult the data sheet of the component and the applicable standard.
Moving a spec sheet between scales
Specification tables mix scales, so a few conversions are worth having at hand. A resistance of 0.5 °F/W is 0.278 K/W, 10 °F/W is 5.556 K/W, and 25 K/W is 45 °F/W. A heat sink listed at 1.2 °C/W is 2.16 °F/W. The same factor applies to the rise: a 40 K rise is a 72 °F rise, and a 36 °F rise is 20 K. For a design limit, convert the limit and the resistance into the same scale first, then compute the allowed power as the allowed rise divided by the resistance. If a junction may rise 90 °F above ambient and the total resistance is 6 °F/W, the allowed dissipation is 15 W. In SI terms the same case is a 50 K rise over 3.333 K/W, which also gives 15 W.
Symbol and reading the unit
The unit is written °F/W, or sometimes °F·W⁻¹. It is not the same as °F·W, a product of temperature and power that has no use here. The denominator is the heat flow in watts, which is a rate of energy transfer, so the whole unit states a temperature difference per rate. A related unit is °F·h/Btu, where the heat flow is in British thermal units per hour. Since 1 W equals 3.412 Btu/h, 1 °F·h/Btu equals about 3.412 °F/W. Check whether a source uses watts or Btu per hour before comparing, because the ratio is more than three. A value of 0.2 °F·h/Btu, for example, is 0.68 °F/W, and the same resistance is 0.38 K/W.
Precision and checking
- Keep source resistance precision.
- Retain finite repeating-factor rounding.
Reference numbers are displayed with up to twelve significant digits. That display does not add precision to a rounded measurement. Keep source and target quantities compatible, confirm symbol case and regional conventions, and round the final result to precision justified by the input. Factors involving π or repeating fractions use finite numerical precision.
Use a working converter
- Thermal resistance converter
- Fahrenheit degrees per watt to Kelvins per watt converter
- Fahrenheit degrees per watt to Kelvins per kilowatt converter
Source and verification scope
The reference values and examples use the versioned unit definitions shared with the linked converters. Source dates identify the stated access or verification scope. A reverse calculation checks arithmetic and direction, but it does not independently verify a definition. Computandum is independent of the cited organizations, and the citations do not imply endorsement of this guide or a real application.