When a gigawatt figure is useful

Tons of refrigeration are the working unit of chiller plants, but when the numbers grow into the hundreds of thousands it becomes easier to compare them with power stations and grids in gigawatts. A district cooling network that serves a city quarter, a campus of data centers, or the planned cooling capacity of a whole region can all be summarized in a single gigawatt figure. This converter takes the tonnage and returns the same rate of heat removal in gigawatts. The default of 10 TR gives 0.0000351685 GW, which shows right away that individual machines are tiny on this scale. The page earns its place with inputs in the thousands or hundreds of thousands, where the result reaches a readable fraction of a gigawatt. For a rough translation, remember that every 284,000 tons add up to about one gigawatt, so a project described as a quarter-million tons is close to 0.9 GW of cooling.

Definition and derivation

A ton of refrigeration equals 12,000 British thermal units per hour. That figure arose from the ice trade: melting one short ton of ice in 24 hours absorbs 288,000 Btu at 144 Btu per pound. With the International Table Btu of 1,055.05585262 joules, 12,000 Btu per hour is 3,516.8528 watts. A gigawatt is a billion watts, so one ton of refrigeration is 3,516.8528 divided by 10 to the 9th, or 3.5168528 times 10 to the minus 6 gigawatts. That is the factor the converter applies, 0.00000351685284207 GW per TR. Because the number is so small, the page is most useful for inputs in the thousands or more. NIST SP 811 lists the Btu and the ton of refrigeration that this derivation relies on.

Checking the order of magnitude

Because several prefixes are involved, a sanity check is worth the thirty seconds. One ton is about 3.5 kilowatts. One thousand tons is about 3.5 megawatts. One million tons is about 3.5 gigawatts. So 100,000 tons should land at about 0.35 GW, which is 350 megawatts, and the converter returns 0.351685 GW for that input. If your own result for 100,000 TR is 3.5 or 0.035, a decimal point slipped. These landmarks also help when you only have the answer in gigawatts and want to translate it back: 0.7 GW of cooling is about 200,000 tons. The exact reverse relationship is that 1 GW equals 284,345 TR, found by dividing a billion watts by 3,516.85 watts per ton, and it is the figure to use when a power-sector report must be restated in the cooling vocabulary.

Data centers and their heat

Nearly all of the electrical power a data center draws is released as heat, so the cooling plant has to remove about as many watts as the IT equipment consumes, plus the heat from fans and power conversion. A facility with 100 MW of IT load needs roughly 100 MW of heat rejection, which is 0.1 GW or about 28,435 TR. A campus that plans 1 GW of total load would need cooling on the order of 284,000 TR before any margin. These are illustrative sums that depend on how the cooling is arranged, and actual plants include redundancy and diversity. They show why large operators talk about gigawatts and why cooling vendors, who think in tons, need conversions between the two vocabularies. Power usage effectiveness, defined as total facility energy divided by IT equipment energy, links the two sides. A facility with a PUE of 1.3 and 100 MW of IT load draws 130 MW in total, with the extra 30 MW going to cooling and power conversion.

District cooling and city-scale plants

District cooling systems pipe chilled water from central plants to many buildings. Their capacity is quoted in tons in North America and in megawatts in much of Europe, the Middle East and Asia. A system of 20,000 TR corresponds to 70.3 MW, or 0.0703 GW. Some of the largest networks reach several hundred thousand tons. Quoting those in gigawatts places them next to power generation: a cooling plant of 0.35 GW removes as much heat as a mid-sized power station produces in electricity. That comparison is only about the size of the numbers, because cooling plants consume far less electricity than the heat they move, thanks to a coefficient of performance well above one.

Cooling capacity versus electric draw

A chiller does not use a gigawatt of electricity to provide a gigawatt of cooling. If its coefficient of performance is 6, it needs one sixth as much electricity, so 0.351685 GW of cooling would draw about 0.0586 GW, or 58.6 MW. Efficiency is also quoted as kilowatts per ton, with efficient large chillers often near or below 0.6 kW per ton at rating conditions. A figure of 0.586 kW per ton is the same as a COP of 6, because 3.5169 divided by 0.586 is 6. The converter only handles the cooling side, so combine its output with an efficiency to estimate electricity. Without that distinction, headlines about gigawatts of cooling are easy to misread as gigawatts of power consumption. In reports, call the gigawatts this page returns cooling capacity or thermal load, and reserve electrical demand for the draw of the compressors, pumps and fans. Both the coefficient of performance and the kW per ton figure belong to the conditions at which they were measured.

Heat rejection at power plants

Thermal power stations reject large amounts of heat, and engineers sometimes describe it in tons. A plant that produces 1 GW of electricity at 33 percent efficiency releases about 2 GW of heat to the environment, which is roughly 568,690 TR. Cooling towers and once-through cooling systems carry that heat away. This is a different use of the tonnage unit from refrigeration proper, and the numbers are illustrative because efficiencies vary by technology. Still, the conversion works, since a ton is just a power. If a source describes condenser duty in Btu per hour, divide by 12,000 for tons and then use this page, or convert Btu per hour to watts directly.

Reading a result in scientific notation

Small inputs produce small outputs. The default result of 10 TR is 0.00003516852842 GW, which the page may show as 3.516852842e-5. The e-5 means the decimal point moves five places to the left. At the other end, 2,500 TR gives 0.0087921 GW, or 8.79 MW. Because gigawatts are enormous next to single machines, the meaningful range for this page starts around ten thousand tons. If your project is smaller, megawatts are a better output unit, and the companion pages for milliwatts and picowatts are meant for the opposite direction, showing how large a ton looks on very fine scales.

Limits and sources

The page converts a rate of heat flow from one unit to another. It does not size plants, estimate loads, compute energy over time or account for the rating conditions that define a machine's nominal tonnage. The relationship between the ton and the watt comes from the Btu definition in NIST SP 811, and any differences with other sources come from using a different Btu. Capacity data for equipment should come from manufacturers and from standards bodies such as AHRI, while load calculations follow methods published by ASHRAE. Use this converter to restate a known capacity in another unit and nothing more. Because tonnage is a nominal rating, a plant of 100,000 TR is a statement about design conditions, not about guaranteed output every hour of the year. In hot weather the delivered capacity can fall, and in mild weather the plant runs below its rating most of the time.

A worked example for a planned district

Suppose a planning study assumes a peak cooling demand of 85,000 TR for a new district. Multiplying by 0.00000351685 gives 0.298932 GW, about 299 MW. If the study applies a diversity factor of 0.8 because not every building peaks at once, the plant is sized for 68,000 TR, or 0.239146 GW. With a plant coefficient of performance of 5.5, the electric draw at peak is about 0.0435 GW, or 43.5 MW. All of these inputs are illustrative assumptions, not data for a real project. The sequence shows how the converter fits into a larger calculation: it restates the cooling capacity in gigawatts, and the diversity factor and the efficiency are applied separately.

Storage is measured in ton-hours

Large cooling systems often include thermal storage, such as chilled water tanks or ice, to move electricity use away from peak hours. Stored cooling is an amount of energy, and the common unit is the ton-hour, equal to 12,000 Btu or about 3.517 kilowatt-hours. A storage system of 100,000 ton-hours holds about 351,685 kWh, which is 0.3517 GWh. A rate in gigawatts, which is what this page produces, and an energy in gigawatt-hours are different quantities. A plant delivering 0.1 GW for four hours moves 0.4 GWh. Keeping the two apart avoids reports that mix a capacity with a quantity of stored cooling.

The same ton in neighboring prefixes

Placing the ton next to its neighbors helps with the order of magnitude. One ton is about 3.5168528 kilowatts, 0.0035168528 megawatts and 0.0000035168528 gigawatts. Each step up the prefix ladder moves the decimal point three places. A chiller of 500 TR is 1.76 MW and 0.00176 GW. A plant of 50,000 TR is 175.8 MW and 0.1758 GW. If the number on the page does not agree with the megawatt estimate you made first, the likely cause is an extra or missing factor of one thousand, and checking the intermediate megawatt value is the fastest way to find it.