Lambda values on insulation labels

Insulation products for homes and buildings carry a declared thermal conductivity, called lambda, usually written as 0.032 W/(m·K) or 32 mW/(m·K). European product standards and many data sheets state it in W/(m·K), while manufacturers of high-performance aerogel and foam often write mW/(m·K) because the numbers are easier to read. A homeowner comparing boards, a contractor checking a spec and a student working a heat-loss problem all meet both forms. This page divides the mW/(m·K) value by 1,000 and returns W/(m·K), so that a label in one form can be put into a calculation or a table that uses the other.

Dividing a conductivity datasheet value by 1,000

The prefix milli means 10^-3, so 1 mW/(m·K) equals 0.001 W/(m·K). The page divides by 1,000. The watt is one joule per second, and the unit combination measures how much heat flows through a layer per meter of thickness and per kelvin of temperature difference. Because only the prefix changes, the conversion is exact. A direct check is moving the decimal point three places left: 32 mW/(m·K) is 0.032 W/(m·K), and 22 mW/(m·K) is 0.022. In reverse, 0.04 W/(m·K) is 40 mW/(m·K). Since the kelvin and the Celsius degree are the same size for differences, a conductivity written per °C is identical numerically.

Ten milliwatts per meter kelvin in W/(m·K)

The default of 10 mW/(m·K) becomes 0.01 W/(m·K). Common insulation values give 0.015 for aerogel-class products at 15 mW/(m·K), 0.022 for polyisocyanurate boards, 0.032 for mineral wool and 0.036 for expanded polystyrene. In the opposite direction, 0.6 W/(m·K) for water is 600 mW/(m·K). These are typical figures from product literature and reference tables, and each product has its own declared value, so check the actual datasheet. The numbers show why the milliwatt form is popular: 22 and 32 are easier to compare by eye than 0.022 and 0.032, and the difference of 10 is visible at once.

Turning conductivity into thermal resistance

The thermal resistance of a layer, in m²·K/W, is its thickness in meters divided by its conductivity in W/(m·K). For 100 mm of a product at 32 mW/(m·K), the conductivity is 0.032 W/(m·K), and the resistance is 0.1 / 0.032 = 3.125 m²·K/W. With 22 mW/(m·K) the resistance of the same thickness is 0.1 / 0.022 = 4.545 m²·K/W. Using the millivalue directly without conversion would produce a result 1,000 times too large, which is why the conversion step matters. A U-value of a wall adds the resistances of all layers and the surfaces, which is a larger calculation than this page performs.

R-values in the United States

American product labels give R-value in ft²·°F·h/BTU. One m²·K/W is about 5.678 of those units. The 100 mm layer at 3.125 m²·K/W corresponds to about R-17.7, and the layer at 4.545 m²·K/W to about R-25.8. A product sold by R-value per inch may state values near R-3.7 for mineral wool and higher for foam boards. Convert a lambda value to resistance for a given thickness first, then to R-value. Watch the unit of the lambda before you start: a figure of 32 entered as 32 W/(m·K) instead of 32 mW/(m·K) would make the layer look like a conductor. The page covers the first step, and conversion of resistance to R-value belongs to a different tool. Keep the thickness with the number, because an R-value without a thickness cannot be compared.

Gases and the 26 mW/(m·K) of still air

Still air has a thermal conductivity of about 26 mW/(m·K) at room temperature, which is 0.026 W/(m·K). Insulation works by trapping gas in small cells so that convection is suppressed, and good products reach 30 to 40 mW/(m·K) with fibers and 20 to 25 with foam cells that hold low-conductivity gases. Argon in a double-glazed window conducts about 17 mW/(m·K), roughly two thirds of air, and that is one reason argon fill is used. These are approximate reference figures at room temperature. Converting each to W/(m·K) lets you compare them with solids like glass at about 1 W/(m·K) and with concrete at around 1 to 2.

Converting W/(m·K) back to milliwatts

To convert the other way, choose watts per meter kelvin as the source and milliwatts per meter kelvin as the target. A value of 0.04 equals 40 mW/(m·K), 0.6 equals 600, and 1 equals 1,000. The page multiplies by 1,000. The same page offers watts per centimeter kelvin and calories per centimeter second degree Celsius, so you can continue a chain if a source uses those. A table with some entries in each form should be normalized to one unit before ranking products, or the order will be wrong: 0.04 is bigger than 22 only when both are in the same unit.

Declared values and aging

The lambda printed on a product is a declared value, derived from tests at a standard mean temperature, usually 10 °C, and with statistical margins. Some foams change over time as gas diffuses in or out, so an aged value can be higher than the initial one, and standards define how to report it. Moisture raises conductivity, and a wet insulation layer performs worse than its label. The converted number inherits those conditions. When you compare two products, make sure both quote the same kind of value, such as the declared or the aged design value, at the same temperature.

Precision and scope of the page

The conversion is exact, so the significant digits follow the input. A declared 32 mW/(m·K) becomes 0.032 W/(m·K), not 0.03200 W/(m·K). The page does not compute a U-value, heat loss, condensation risk or compliance with an energy code. Those depend on the full assembly, climate and local rules. Use the page to express a conductivity in the unit required and consult the relevant standard or a qualified designer for the building. When you enter a declared value from a product sheet, copy it with its test temperature and thickness range, because the same product line can list different lambda values for different densities.