Air conditioner nameplates in tons and BTU/h
Residential and commercial cooling equipment in the United States is sold by tonnage, and the nameplate or spec sheet lists the same capacity in BTU per hour. A homeowner comparing a 3-ton condenser with a quote that says 36,000 BTU/h, or a contractor checking a submittal, needs to move between them. This page multiplies tons of refrigeration by 12,000 and returns BTU IT/h. The factor is a plain integer, so the arithmetic is simple, but quotes use the two units interchangeably and sometimes drop the word per hour, which leads to confusion. The page labels both units in full. This matters when the quote is read aloud or typed into a form, where BTU alone can be mistaken for a total energy rather than a rate.
Why a ton is 12,000 BTU per hour
The unit comes from the cooling effect of melting ice. Melting one US short ton of ice, 2,000 pounds, absorbs about 288,000 BTU, since the heat of fusion of water is about 144 BTU per pound. Spread over 24 hours, that is 12,000 BTU per hour, which became the definition of one ton of refrigeration. No ice is involved in the modern use of the unit, and a ton in this sense is a rate of heat removal, not a mass. The page uses the International Table BTU, and the equivalent is about 3.517 kW. Equipment catalogs often print both figures side by side, such as 36,000 BTU/h and 10.55 kW, and the page lets you confirm that they match. The factor is a definition, so results carry no error beyond your input.
Ten refrigeration tons in BTU per hour
The default 10 TR returns 120,000 BTU IT/h. That is the scale of a rooftop unit serving a small shop or a restaurant, and well above a house, where 2 to 5 tons is more common. The result is easy to check because the factor is 12,000: the result is the input times twelve, followed by three zeros. If a value you enter as 10 gives 12, you divided instead of multiplying, and if it gives 1,200,000 the decimal point slipped by one place. The default is also a convenient test value for a spreadsheet formula that carries the same factor. A 10-ton packaged rooftop unit of this size is typical of a small retail space, while a large office building runs hundreds of tons through chillers.
Common residential sizes
Residential systems usually come in half-ton steps. A 2-ton unit is rated at 24,000 BTU/h, a 3-ton unit at 36,000 and a 5-ton unit at 60,000. A 2.5-ton system, popular for mid-sized homes, is 30,000 BTU/h. These nominal sizes are labels: the capacity at actual operating conditions can differ from the nameplate figure. Entering 1.5 gives 18,000 BTU/h, which is a common size for a ductless system or a small zone. When you compare quotes, convert each to the same unit and check the model numbers, since many manufacturers encode the capacity in thousands of BTU/h within the model name. For example, a model number containing 36 usually means about 36,000 BTU/h, which is 3 tons, though you should confirm it on the nameplate.
Mini-split labels and half-ton fractions
Ductless mini-split units are often labeled by BTU/h only, such as 9,000, 12,000 or 18,000. Divide by 12,000 for the tonnage by selecting BTU per hour as the source and TR as the target: 9,000 is 0.75 TR, 12,000 is 1 TR, and 18,000 is 1.5 TR. Some labels are marketing sizes, so the actual rated capacity may differ a little from the number printed. A 24,000 BTU/h unit equals 2 TR. The page gives the straight arithmetic, and the efficiency rating, such as SEER2 or EER, is a separate figure that this conversion does not touch. Choosing between a 12,000 and an 18,000 unit for a room depends on the load, the insulation and the sun exposure, and the conversion gives only the equivalent tonnage of each.
From BTU per hour to kilowatts
European and international documents rate cooling in kilowatts. One ton of refrigeration is about 3.517 kW, so 36,000 BTU/h, which is 3 TR, comes to about 10.55 kW. A 2-ton unit gives 7.034 kW, and a 5-ton unit gives 17.58 kW. To go through this chain, multiply the tons by 3.517 and compare. People sometimes confuse this kilowatt figure with the electrical power the unit draws, which is much lower, and the two must be kept apart on every spec sheet. The power rating is 3,516.85 W of heat removal per ton, and the unit draws a fraction of that as electricity.
Cooling capacity is not the electrical draw
A cooling rating describes heat moved, while the electricity consumed is a separate figure. The energy efficiency ratio, EER, is the cooling output in BTU/h divided by the electrical input in watts. An illustrative unit of 36,000 BTU/h with an EER of 12 draws about 3,000 W. The same unit at an EER of 10 draws 3,600 W. This page converts only the cooling side, from tons to BTU/h. To estimate running cost, use the electrical input from the nameplate or the datasheet, and multiply by hours of use and the price of electricity.
Rated capacity depends on conditions
The nameplate capacity is measured under standardized indoor and outdoor temperatures and humidity, and the actual output changes with the weather and the airflow. A system rated at 3 tons may deliver less on a very hot day and more on a mild one. The conversion keeps the nominal number consistent between units and does not predict that behavior. When you compare equipment from different makers, make sure the ratings refer to the same test standard, and look at the stated conditions in the datasheet. A rating in tons without conditions is a label more than a measurement.
Sizing needs a load calculation
Choosing a system size is a separate task from converting units. In residential work, a heat-load calculation, such as the ACCA Manual J procedure, accounts for climate, insulation, windows, orientation, ducts and occupancy. Rules of thumb based on floor area can be off by a wide margin, and an oversized unit cycles on and off and removes less moisture. Use the page to translate numbers between a load report in BTU/h and equipment in tons, then ask a qualified contractor to confirm the selection. The figure of 120,000 BTU/h for 10 tons says what the equipment can do, not what a building needs.