Why the ton survives in cooling
Air conditioners, chillers and cold-storage plants are still sold by the ton in the United States, in India, in the Gulf states and in a good part of Asia, while engineers and utilities elsewhere think in kilowatts. A project that crosses those boundaries needs a clean conversion. This page turns a rate of heat removal in kilowatts into tons of refrigeration (TR). It uses the factor 0.284345136094 TR per kilowatt, which gives 2.843451360939951 TR for the default 10 kW. The unit lists include watts, megawatts, BTU per hour and both horsepower types, so you can start from any of them. A ton here is a unit of power or heat flow, not of weight. It describes how fast heat is removed, and a unit rated at 3 tons removes 36,000 BTU of heat each hour at the stated conditions.
Where the ton came from
The name comes from the ice trade and early mechanical refrigeration. One ton of refrigeration is the heat removal rate that would freeze one short ton, 2,000 pounds, of water at 0 °C into ice at 0 °C in 24 hours. The latent heat of fusion of ice is about 144 BTU per pound, so melting or freezing 2,000 lb takes 288,000 BTU, and spread over 24 hours that is 12,000 BTU per hour. That figure is the modern definition: 1 TR = 12,000 BTU(IT)/h. With one international table BTU equal to 1,055.05585262 J, the ton is 12,000 × 1,055.05585262 / 3,600 = 3,516.8528421 W. So 1 TR is about 3.517 kW, and the reverse factor is 1 divided by 3.5168528, which is 0.2843451. The ice story is historical, and the number 12,000 is what engineers use.
The default example and a few anchors
With the default input of 10 kW, the result is 2.843451360939951 TR, a little under three tons. A few anchor values make the scale intuitive. One ton is 3.517 kW. Three tons is 10.55 kW, which equals the 36,000 BTU/h rating on a typical residential central air conditioner. Five tons is 17.584 kW, a large home or a small commercial rooftop unit. A 100 TR chiller removes 351.7 kW of heat, and a 1,000 TR plant handles 3.517 MW. Going the other way, if a Gulf-region specification lists a cooling load of 52 kW for a server room, divide by 3.5169 to get about 14.8 TR. The reverse conversion multiplies by 3.5168528: 7.5 TR is 26.376 kW. These numbers describe heat flow, so they apply to the heat removed from the space, not to the electricity bill.
Cooling kilowatts versus electrical kilowatts
The most common mistake with this conversion is to treat cooling capacity in kW as electrical input in kW. They are different quantities measured in the same unit. A heat pump or air conditioner moves heat, and the cooling output divided by the electrical input is the coefficient of performance, COP. If a 10.55 kW cooling unit (about 3 TR) has a COP of 3.5 at rating conditions, it draws about 3.0 kW of electricity. In US practice the same ratio appears as EER, which is BTU/h of cooling per watt of input, and chiller plants are often described by kW of input per ton of cooling. Dividing 3.517 kW per ton by the COP gives that figure: a COP of 5.86 corresponds to 0.6 kW/TR. When a catalog lists both numbers, the page should be applied to the cooling figure only.
A worked example for a server room
Suppose a small server room has 14 kW of IT equipment drawing power, almost all of which becomes heat inside the room, and lights and people add 1 kW. The heat load is about 15 kW. Entering 15 kW gives 15 × 0.284345136 = 4.265 TR. Rounding up to the next common equipment size would suggest a 5 TR unit, which provides 17.58 kW and leaves about 17 percent margin. A designer will also consider redundancy, humidity control and future growth, none of which this page addresses. A second example works in the opposite direction: a 7.5 kW split unit converts to 2.1326 TR, which a US reader would call a 2 ton unit at 24,000 BTU/h, since 2 TR is 7.03 kW and this unit is slightly above that. These figures are illustrative loads, not a design recommendation.
Which BTU is in the ton
The ton is tied to the BTU, and the BTU has several definitions. The international table BTU used by the ASHRAE and HVAC industry is 1,055.05585262 J. The thermochemical BTU is 1,054.35 J, and a BTU at 59 °F is about 1,054.8 J. Each one gives a slightly different ton. Using the thermochemical BTU, 12,000 BTU/h is 3,514.5 W rather than 3,516.85 W, a difference of about 0.07 percent. The page uses the international table value, which matches standards in the field. In practice the difference sits far below the accuracy of a cooling capacity rating, which depends on rating conditions such as the outdoor and indoor air temperatures and humidity. A manufacturer's published capacity is valid at its stated conditions, and the capacity falls as outdoor temperature rises.
Heat rejection is larger than cooling
A chiller or air conditioner rejects more heat outdoors than it removes indoors, because the compressor work also ends up as heat. For a 100 TR water-cooled chiller at 0.6 kW per ton, the cooling is 351.7 kW and the compressor draws about 60 kW, so the condenser must reject roughly 411.7 kW. In tons, that is 117.1 TR of heat rejection. Cooling tower sizing therefore uses heat rejection, not the nominal tonnage. The converter works for either figure as long as the input is a heat flow in kilowatts. A common rule of thumb in cooling tower practice is about 15,000 BTU/h of rejection per nominal ton, which equals 4.40 kW per TR and agrees with a typical compressor input of about 0.9 kW per ton on top of the 3.517 kW of cooling. Treat such rules as approximations.
Tonnage versus weight tons
Readers new to HVAC are sometimes confused when a "3 ton" air conditioner weighs 200 pounds. The ton in the name measures capacity, not mass. A condenser unit for 3 TR may have a shipping weight of a few hundred pounds, a chiller rated 500 TR may weigh many tons, but the two numbers are unrelated. A different confusion arises in refrigerant quantity: the refrigerant charge is measured in pounds or kilograms. A third arises with the metric tonne, which is 1,000 kg and plays no role here. The ton of refrigeration also should not be mistaken for the short ton of ice in the original definition, since that definition is only a bridge to the BTU figure. This converter involves no mass at all, only a rate of energy per time, and so the same input in kW always gives the same TR.
Accuracy and the sizing trap
Converting a load from kW to tons is exact, but sizing equipment from the result is not. Equipment comes in discrete sizes, capacity varies with outdoor temperature, and load calculations carry assumptions about occupancy, glazing, ventilation air and internal gains. A unit chosen exactly at 2.84 TR for a 10 kW load would have no margin, whereas an oversized unit cycles on and off and controls humidity poorly. Methods such as ACCA Manual J for homes and ASHRAE load calculation procedures exist for this reason, and they give the load in BTU/h or kW before conversion. The converter output should be rounded sensibly. Four significant figures is plenty, so 10 kW is 2.843 TR. Quoting 2.843451360939951 TR in a report suggests an accuracy that no load calculation has.
Limits of the conversion
The page converts between power units and nothing else. It assumes that the entered number is a rate of heat flow or power, and it does not calculate installation limits, equipment ratings, protection, material response or compliance. It does not size ductwork, piping or refrigerant, and it does not account for latent versus sensible load, altitude, part-load behavior or the electrical supply. A capacity quoted in kW without conditions is incomplete, and a ton rating without the outdoor and indoor temperatures is too. Use the result to compare documents that use different units, and take sizing decisions from a proper load calculation and the manufacturer data for the chosen equipment.
Turning electrical loads into tons
Almost every watt of electricity used by equipment in a room ends up as heat in that room, which makes kilowatts of equipment load easy to convert into cooling load. One kilowatt of electrical load releases 3,412 BTU/h, which is 0.2843 TR, consistent with the factor used here. A rack of servers drawing 8 kW adds 2.275 TR of cooling demand, and 14 kW of IT equipment adds about 3.98 TR. Lighting adds its wattage, people add heat as well, and sunlight through windows adds more. Motors inside the conditioned space contribute their input power, but a motor that drives a fan or pump outside the space contributes only the losses that fall inside. This page only changes the unit. Estimating the heat gain of each item is up to whoever knows the equipment, and the arithmetic of turning kW into tons is the same for every item, so the tonnage can be summed afterwards.
From tons to chilled water flow
Once a load is known in tons, designers often ask how much water the coil needs. The heat balance is power equals mass flow times specific heat times temperature rise. With water at 4.186 kJ/(kg·K) and a 5 K rise, a 10 kW load needs 10 / (4.186 × 5) = 0.478 kg/s, about 28.7 liters per minute. In US units, the rule of thumb is BTU/h equals 500 times gpm times the temperature rise in degrees F, so a ton at a 10 °F rise needs 12,000 / (500 × 10) = 2.4 gpm. A 10 kW load is 2.84 TR and needs about 6.8 gpm at that rise. The two routes agree because they describe the same physics in different units. The factor 500 assumes water near room temperature, and glycol mixtures have a lower heat capacity than water, so they need somewhat more flow per ton.