Moving older conductivity data into SI
Thermal conductivity in W/(m·K) is the unit of building codes, materials databases, simulation software and product certificates. Before SI took over, many handbooks, geology texts and chemistry references listed conductivity as cal/(cm·s·°C), and a lot of that data is still cited. A reader who finds copper at about 0.93 or granite at 0.006 in an old source needs the SI figure to use it in a model. This page performs the conversion with the exact definition of the thermochemical calorie, so older values become directly usable in any current tool that expects watts per meter kelvin. Geothermal and permafrost studies are a typical case: ground heat flow was once reported in microcalories per square centimeter per second, with conductivities of rocks in matching calorie units, and the SI figures are needed for current ground-source heat pump design.
How 418.4 is built
Start with 1 cal th/(cm·s·°C). The calorie becomes 4.184 J. One centimeter in the denominator is 0.01 m, so dividing by it multiplies by 100. A second is unchanged, and joules per second are watts. A Celsius degree interval is one kelvin. The result is 4.184 times 100, or 418.4 W/(m·K). Both the calorie and the centimeter are exact definitions, the first in NIST SP 811 and the second through the meter. The SI Brochure defines the derived unit as watt per meter kelvin, and there is no further uncertainty in this factor. Thermal engineers sometimes remember the shortcut that 1 W/(m·K) is about 0.00239 in calorie units, which is the reciprocal of 418.4 and works for rough checks.
The default and its impossibility
The converter starts at 10 and returns 4,184 W/(m·K). That is twice the conductivity of diamond, so no real material matches it. The default is best read as an arithmetic demonstration. More realistic inputs in the calorie system run from about 0.00006 for air to about 1 for the best metals. Entering 0.96 gives 401.664 W/(m·K), close to the roughly 401 W/(m·K) usually quoted for copper at room temperature. Entering 0.5 gives 209.2, in the range of aluminum alloys. A result near 200 W/(m·K) for an alloy label such as 6061, which is often listed around 167, is a reminder that alloying lowers conductivity compared with pure metal. Entering 0.0024 gives 1.004, similar to ordinary glass. Entering 0.04 gives 16.736, in the range of stainless steel, and 0.002 gives 0.8368, similar to brick.
Building and soil examples
Heat flow in buildings and ground is where SI conductivity is used daily. Water is about 0.6 W/(m·K), or 0.00143 in the calorie unit. Masonry and concrete commonly fall between about 0.5 and 2 W/(m·K), and soils between roughly 0.3 and 3 depending on moisture and mineral content. A masonry handbook giving the conductivity of dry sand as 0.0006 cal th/(cm·s·°C) corresponds to 0.251 W/(m·K), and a granite value of 0.006 is 2.51 W/(m·K). These conversions place old measurements in the same units as design values in modern guides. A designer can then compare a measured value for a local stone with tabulated values in a building physics standard, using one unit throughout.
The reverse trip
To move from SI back to the calorie system, select Watts per meter kelvin in the From menu and the calorie unit in the To menu. The page divides by 418.4. Thus 0.6 W/(m·K) gives 0.001434, 237 W/(m·K), a common figure for pure aluminum, gives 0.5664, and 16 W/(m·K), typical for austenitic stainless steel, gives 0.03824. This direction suits anyone who has to enter a modern value into a legacy code, or who is working through a textbook problem set that uses calories and centimeters throughout. Because the multiplier is exact, a round trip returns the starting number, so converting 0.0014 to 0.58576 and back gives 0.0014 again.
A worked heat-flow example
Suppose a wall layer has conductivity 0.0014 cal th/(cm·s·°C), which converts to 0.58576 W/(m·K). For a 0.2 m thick layer with 15 K across it, heat flux is 0.58576 times 15 divided by 0.2, which is 43.9 W/m². Doing the same calculation without converting would mix centimeters and meters and produce an answer that is wrong by orders of magnitude. The conversion ahead of the calculation is the safe order, and the page gives the number you carry into the flux formula. If the temperature difference is quoted in Fahrenheit degrees, multiply it by 5/9 to get kelvins first, since the formula needs the difference in kelvins or Celsius degrees.
Limits that the converter cannot see
A single conductivity number hides many conditions. Moisture content raises the value for porous materials, temperature changes it for nearly all, and direction matters for wood, composites and layered rock. Contact resistance between layers is not part of material conductivity. The page converts the value you type and nothing else, so confirm that the source value matches your material, temperature and moisture state before using the converted number. For wood the value also depends on grain direction, and for compacted soil on dry density.
Confusions between similar units
Thermal conductivity, thermal conductance and heat transfer coefficient look alike in print. W/(m·K) is conductivity. W/K is conductance of a specific object, and W/(m²·K) is a surface or U-value coefficient. A building U-value of 0.3 W/(m²·K) cannot be converted with this page, because the dimension differs. Check that the original unit contains a length in the denominator before applying the 418.4 factor. A related unit, the BTU·in/(h·ft²·°F), often quoted as a k-value in US insulation data, is a conductivity and equals about 0.1442 W/(m·K), but it needs its own converter.
Reporting converted values
Because 418.4 is exact, report the converted number to the precision of the source. Handbook values are usually good to two or three digits, so 401.664 should be written as about 402 W/(m·K). A result quoted as 0.25 W/(m·K) for soil says honestly how well the value is known.