A unit pair from opposite ends of the scale

A terawatt measures global-scale power, such as the total rate at which humanity uses energy or the output of the entire electricity grid of a large region. A ton of refrigeration measures the cooling capacity of a single air conditioner or chiller. Few problems involve both at once, but they do come up when someone wants to express a very large cooling demand in the units the equipment industry uses, or to compare the size of a national cooling load with typical machines. This page performs that conversion. Enter a power in terawatts and get the equivalent in tons of refrigeration (TR). The calculation is one multiplication, and the factor is derived from defined values, so the result is as exact as the digits you provide. Policy discussions about future cooling demand often talk about gigawatts of electric load and billions of air conditioners, and a converter that links watts to tons makes it easy to translate between the two vocabularies. Equipment catalogs, tender documents and building codes in the United States still use tons, so a figure from an energy agency report in terawatts must be translated before it can be compared with a chiller schedule.

What a ton of refrigeration is

The ton of refrigeration comes from the era of ice-based cooling. It is the heat absorbed when one short ton, 2,000 pounds, of ice at its melting point turns to water in 24 hours. With a latent heat of fusion of 144 Btu per pound, that is 288,000 Btu per day, or 12,000 Btu per hour. Converting with the International Table Btu of 1,055.05585262 joules gives 12,000 times 1,055.05585262 divided by 3,600, which is 3,516.8528 watts, or 3.5168528 kilowatts. In metric terms that is roughly 3,024 kilocalories per hour. The ton in the name refers to ice weight and has nothing to do with the mass of the machine. The unit is easy to confuse with the metric ton or tonne, which is a mass of 1,000 kilograms, and with the long and short tons of weight. The refrigeration ton is a rate, equal to a power, and is written TR or RT in drawings. Because 1 TR is about 3.517 kW, a 5-ton unit has a cooling capacity of 17.58 kW.

Deriving the factor

Start from 1 TR equals 3,516.852842 W. One terawatt is 10 to the 12th watts. Dividing gives 10 to the 12th over 3,516.852842, which is 284,345,136.094 TR per terawatt. So a power of 1 TW equals about 284 million tons of refrigeration. The page multiplies by this number. For a reverse conversion, divide a tonnage by 284,345,136.094, or multiply by 3.516852842 times 10 to the minus 9, to get terawatts. The relationship is accurate to the digits of the Btu definition, and the inch-pound standards that define the Btu are the root of any rounding differences between sources. Always check which Btu a source assumes, because the thermochemical and International Table values differ slightly. Check the factor by rounding: 10 to the 12th divided by 3,517 is about 284.3 million, which agrees with 284,345,136. A calculator that returns a value far from 284 million per terawatt has either lost a power of ten or used the wrong unit for the ton.

The default of 10 TW

With 10 TW as input the result is 2,843,451,360.94 TR, about 2.84 billion tons of refrigeration. That figure helps to picture how large 10 TW is. World primary energy supply is of the order of 18 to 20 TW when averaged over a year, according to commonly cited international statistics, so 10 TW is more than half of that. Expressed in the unit of air-conditioning, it would take nearly a billion 3-ton home air conditioners running flat out to move that much heat: a 3-ton residential unit rates 36,000 Btu per hour, or 10.55 kilowatts, so 10 TW is about 948 million of them. The default is chosen for easy checking rather than realism. The same number can be read as 2.84 times 10 to the 9th TR, which is a convenient way to write it in a report.

More realistic scales

Cooling plants are measured in megawatts and gigawatts. A 500 MW heat load is 0.0005 TW, and entering that gives 142,172.57 TR. A 2 GW load, which is 0.002 TW, equals 568,690.27 TR. The cooling load of a large data center campus can reach tens or hundreds of megawatts, and district cooling plants in large cities are rated in tens of thousands of tons. A single large water-cooled centrifugal chiller may be rated at 1,000 to 3,000 TR. Quoting such equipment in terawatts would be unwieldy, so engineers use kilowatts or tons. The terawatt version is useful in policy contexts, where it is natural to ask what share of global power flows the cooling sector represents. A residential split system of 2 TR has a nominal capacity near 7.03 kW, so 142,172.57 TR is the cooling capacity of about 71,000 such units. For a 500 MW heat rejection at a power plant, which is a different thing from cooling capacity, the same conversion expresses the amount of heat in the unit of the cooling industry.

Cooling capacity is not electrical power

A ton of refrigeration measures heat removed, not electricity consumed. A chiller with a coefficient of performance of 6 removes six units of heat for every unit of electrical energy it uses. A 1,000 TR chiller removes 3,516.85 kW of heat and draws about 586 kW of electricity at that COP, which equals 0.586 kW per ton. Equipment catalogs often quote efficiency in kW per ton, and lower is better. When you convert a terawatt figure, check whether it describes thermal load or electric supply. The converter makes no distinction between them. It reads the number as watts of heat flow. A terawatt of electricity could drive several terawatts of cooling.

Ratings come with conditions

The tonnage on a nameplate holds for stated test conditions. In the United States, AHRI standards fix entering water and air temperatures, flow rates and fouling allowances for rating chillers and unitary equipment, and the same machine will deliver different capacity in a hot climate or with dirty coils. The factor on this page converts power units and says nothing about how much cooling a machine really delivers on a hot afternoon. For design work, use manufacturer performance data at your design conditions. The unit conversion gives you a consistent label for the quantity, while the engineering requires load calculations such as those in ASHRAE handbooks. A unit sold as 3 tons has a nominal capacity of 36,000 Btu per hour, but the delivered value in operation depends on outdoor temperature and airflow, and the rating sheet should be read for the actual capacity at your conditions.

Global comparison, with care

Putting global quantities into cooling-industry units invites playful comparisons, so it helps to keep them honest. The sunlight reaching the top of Earth's atmosphere is commonly cited as roughly 170,000 TW, a number that works out to about 4.8 times 10 to the 13th tons of refrigeration. Human primary energy use of about 19 TW equals roughly 5.4 billion TR. These are order-of-magnitude values from commonly cited sources, and the conversion is exact only for the number you enter. The point is scale, not precision. Any statement built on them should cite the original dataset and its year, since both energy use and solar estimates are revised. Another viewpoint is per person. With about 8 billion people and 19 TW of primary energy, the average is roughly 2,400 W per person, or about two thirds of a ton of refrigeration.

Rounding and reading large outputs

Results with ten digits are common on this page. Round to the precision of the input before sharing the number. If the terawatt value is rounded to one significant figure, saying 2,843,451,360.94 TR overstates certainty, and 2.8 billion TR is more honest. When you need to compare with equipment, convert to megawatts or kilowatts as a middle step: 1 TW is 1,000,000 MW, and 1 MW is about 284 TR. That relationship gives a handy sanity check, because a 3,516.85 kW chiller is 1,000 TR and a 1 MW chiller is about 284 TR. If the tool shows scientific notation for extreme values, read the exponent first. Spreadsheet users can combine two factors: multiply terawatts by 1,000,000 for megawatts, then by 284.345 for tons per megawatt. Doing it in two steps makes each step easy to audit, and the product reproduces the single factor on the page.

Scope of the tool

The page changes the unit of a power value. It does not size equipment, estimate cooling loads, or evaluate energy use. It also does not distinguish between the US ton of refrigeration and other historical definitions, and some regions and manufacturers use slightly different tons. The page assumes the 12,000 Btu per hour definition. For equipment specification, rely on manufacturer data and standards from bodies such as AHRI and ASHRAE. It does not convert tons of refrigeration to electric load or to annual energy use. To estimate energy, multiply the load by hours of operation and divide by the efficiency of the equipment, steps that need data this page does not have. Treat TR here as a name for a rate of heat flow.