Megaohm is the working unit of insulation testing

Most field insulation testers, often called megohmmeters, display in megaohms, and a lot of maintenance paperwork for motors, cables and switchgear is written in the same unit. A bench instrument or a component datasheet may instead state a figure in teraohms. To compare them, convert one into the other. The page multiplies the teraohm value by 1,000,000 and returns megaohms, so the default 10 TΩ becomes 10,000,000 MΩ. That number is the one to type into a maintenance log that has a single resistance column. Use it when a high-grade reading from a laboratory instrument has to sit beside records from a field tester.

The multimeter ceiling

A typical handheld digital multimeter measures resistance up to about 40 or 50 MΩ on its highest range, and many have an input impedance of 10 MΩ when measuring voltage. Those figures are small next to a teraohm. A 1 TΩ path is 1,000,000 MΩ, so an ordinary multimeter reads it as an open circuit. When someone says a surface is infinite on the meter, the real value could be anywhere above the range limit, from 100 MΩ to many teraohms. Converting a specialized reading to megaohms shows how far beyond a multimeter it is, and why separate high-resistance equipment exists.

Working through the default

To get from 10 TΩ to megaohms, use 10 × 10^12 Ω divided by 10^6 Ω per megaohm, which equals 10 × 10^6 MΩ. The same step works for other values: 0.25 TΩ is 250,000 MΩ, 1.5 TΩ is 1,500,000 MΩ and 3 TΩ is 3,000,000 MΩ. The result keeps the original digits and moves the decimal point six places to the right, because the prefixes tera and mega differ by a million. Writing the number with thousands separators makes six-digit shifts easier to check, and the page returns plain digits you can paste into a sheet without reformatting. A sheet that stores megaohms can then chart high-resistance trends from lab and field data on one axis.

Loading a node with a 10 MΩ meter

Meter input impedance affects what you read. If a node has a source resistance of 1 MΩ and you measure it with a 10 MΩ input, the meter and source form a divider that reads about 91 percent of the true voltage, since 10 divided by 11 is 0.909. If the source were 1 TΩ, the reading would collapse to roughly one millionth of the real value. Converting source resistance to megaohms puts it on the same scale as the meter impedance, which is how loading errors are estimated. For teraohm sources, an electrometer with a far higher input impedance is the right instrument.

Megaohms back to teraohms

Switch the source to megaohms and the target to teraohms to divide by one million. A leakage specification of 500,000 MΩ equals 0.5 TΩ, and 20,000,000 MΩ equals 20 TΩ. Datasheets from different manufacturers mix the two styles, so a purchasing comparison can involve a part rated at 100,000 MΩ and another at 0.2 TΩ. Putting both in megaohms gives 100,000 and 200,000, and the second part has twice the rating. The page makes that comparison a single step, though the test conditions behind each figure, such as voltage and time, still need to match. Read the footnotes first, since one maker may quote a minimum at 100 V and another at 500 V, and the two numbers are not interchangeable.

Reading versus rating

A megaohm figure from a tester is only meaningful with its test voltage and duration. The same cable can read differently at 500 V and at 1,000 V, and values often rise as the voltage is held. Many maintenance procedures use a one-minute reading, and some compare a ten-minute value with a one-minute value as a ratio. The converter does not apply any of those methods. It restates the resistance in another prefix. Record the voltage and the time next to the converted number so that a later reading is comparable, and follow the pass criteria given by the equipment maker or the governing standard. Temperature matters too, because insulation resistance usually falls as the winding or cable warms up, so the same part can read quite differently on a cold morning and after a long run.

A mistake that costs a factor of a million

A frequent error is confusing M and T, or M and m, when copying a reading. 10 MΩ and 10 TΩ differ by a factor of one million, while 10 mΩ and 10 MΩ differ by a factor of 10^9. The error tends to appear when a report template has a fixed unit column and the technician enters the number as it appeared on the display. A habit that helps is to write the unit symbol next to every transcribed value and to convert at the last moment, using this page or a sheet formula, rather than doing the shift mentally.

Leakage current at 1,000 V

The page returns a resistance expressed in a different prefix. It does not test an installation, tell you whether a motor winding is acceptable, correct a reading to a reference temperature or estimate leakage current. For the current, divide the applied voltage by the resistance in ohms. At 1,000 V across 10 TΩ the current is 100 pA, while across 10 MΩ it would be 100 µA. Because the factor is defined by the SI prefixes, results are exact, and any disagreement with a colleague's figure is a rounding choice or a transcription slip. When two sources disagree by exactly a factor of 1,000 or 1,000,000, suspect a prefix before suspecting either instrument.

Setting limits in a maintenance record

A maintenance record often carries a single minimum acceptable value in megaohms. Suppose a lab reading of 0.35 TΩ has to be checked against a minimum of 100 MΩ. In megaohms the reading is 350,000 MΩ, which is 3,500 times the minimum. Written that way, the margin is obvious, and the record does not need a footnote explaining the teraohm unit. Use the same approach when an instrument has an auto-ranging display and the reading moves between units across visits. Fixing the unit in the record makes trends legible. A downward trend in megaohms over several tests is more informative than any one number, and the converter keeps all of them comparable. The minimum itself comes from the equipment maker or the governing standard, not from this page.