Cooling tons next to electronic loads

Air-conditioning and chiller equipment in North America is sold by the ton of refrigeration, while the equipment it cools is described in watts or milliwatts on component data sheets. A technician sizing cooling for a network closet, a lab bench or a small control room adds many small loads and compares the sum with a unit rated at one ton or less. This page converts a milliwatt figure into tons, so a small load can be placed on the same scale as the cooling capacity. The values for single components are tiny, which is the point: they show that a part is negligible, or that a long list of parts is not. The page is built for quick checks while a heat-load table is being filled in.

What a ton of refrigeration is

One ton of refrigeration is the rate of heat removal that melts one short ton (2,000 pounds) of ice in 24 hours. In the units used for ratings, it is 12,000 BTU IT per hour. Since one BTU IT per hour is 0.2930710701722222 W, one ton equals 3,516.852842066667 W, or 3,516,852.84 mW. The page therefore applies TR = mW × 2.84345136094 × 10^-7. The unit has nothing to do with weight in the modern sense; it is a rate of cooling. A residential system of three tons removes up to 36,000 BTU/h, which is 10,550,558.5 mW, or about 10.55 kW. NIST SP 811 lists the conversion for this unit.

Standby loads on a cooling scale

The page opens with 10 mW and returns 0.0000028434513609 TR, or about 2.84 × 10^-6 TR. Think of it as a sleeping sensor, an indicator LED or the leakage of a switched-off device. A 500 mW module gives 0.000142173 TR, and a 10 W unit, entered as 10,000 mW, gives 0.00284345 TR. These numbers sit far below one ton, which is typical. The conversion is useful for showing how many such devices it takes to matter: roughly 351,685 loads of 10 mW each would add up to one ton. That comparison helps a designer decide whether to include a minor load in a table or to leave it among the rounding.

A server rack in tons

A rack of equipment that draws 5 kW produces about 5,000 W of heat, nearly all of the electrical input. That is 5,000,000 mW. Entering that figure gives 1.42172568 TR, which is more than one ton of cooling for a single rack. The result shows why even a modest rack needs dedicated cooling, and why small rooms with a few racks can exceed a household unit. A smaller case, a network cabinet with 1,200 W of equipment, is 1,200,000 mW, or 0.341214 TR. Use measured or nameplate input power, and add the heat from lighting, people and the building envelope to size a unit properly. Tons are only the rating scale.

From tons back to milliwatts

To convert a cooling rating into milliwatts, select tons of refrigeration as the source unit. A 2 ton unit corresponds to 7,033,705.68 mW, which is 7.03 kW. A 1.5 ton unit, which is 18,000 BTU/h, is 5,275,279.26 mW or 5.28 kW. These are heat-removal capacities, not electrical input. The compressor and fans of an air conditioner draw far less electricity than the heat they move, since the heat comes from the space and the electricity runs the cycle. A ratio often called the coefficient of performance, or the energy efficiency ratio in BTU per watt-hour, links the two, and the page does not include it. It converts only units of power.

Rated capacity versus real conditions

A nameplate capacity applies at a specific set of test conditions, such as indoor and outdoor temperatures and humidity defined by a rating standard. On a hot day or at high humidity, a unit delivers less. Converting the nameplate to milliwatts or watts does not alter that. When comparing the load from a heat table with the rating, leave a margin as your design practice and local code require. For room cooling, the sensible heat of electronics and the latent heat from people and outside air enter separately, and a unit has a split between the two. A conversion cannot tell you that, so use the method of a recognized load calculation for a final size.

Ton, BTU/h and kilowatt on one label

Cooling equipment labels often show several units. A window unit may say 12,000 BTU/h, 1 ton and 3.5 kW of cooling in different documents. All three are the same rate within rounding: 12,000 BTU IT/h is 3,516.85 W. Some regions, especially outside North America, list only kilowatts. If you have a milliwatt figure from a data sheet and a ton figure from the label, the page puts them on one scale, and you can convert both to watts. Take care with the word ton. A metric ton of refrigeration, used in some countries, is not the same as the US unit, and the page uses the US value of 3,516.852842 W.

Small loads that add up

A list of small items can look harmless one by one. Forty sensors of 250 mW each are 10,000 mW, a switch is 25 W, and a gateway is 12 W. The total is 47 W, which is 47,000 mW and 0.0133646 TR. Converting each line to the same unit allows a sum without mistakes. Spreadsheet users can enter all values in milliwatts, convert the total once with this page and compare with the cooling capacity. If the total exceeds a small fraction of the unit, look at the largest items first, since they will dominate. Round only at the end, and note which values come from measurement and which from a data sheet.

Why this does not size an HVAC system

The conversion states a power in a different unit. It does not size a cooling system, estimate heat gain from the building, account for efficiency or humidity or confirm that equipment fits an enclosure. Power consumed by a device is treated by the converter as the number you type, and whether all of it becomes heat is for you to decide. Refrigeration capacity ratings come from standards such as those of AHRI in the United States, which define test conditions. For purchases and designs, use the documents of the manufacturer, the local code and a qualified engineer, and use the page for unit consistency.