Two readings from the same switchgear
A maintenance report for a circuit breaker usually holds two very different resistance figures. The closed contacts of each pole are checked with a micro-ohmmeter and read in microohms, often somewhere between tens and a few hundred. The insulation between the live parts and the frame is checked with a megohmmeter and reads in gigaohms. Both are resistances, yet they live at opposite ends of the scale, and a table that mixes them without a common unit is hard to scan. This page converts the small figure to gigaohms, so a contact reading of 80 µΩ appears as 8e-14 GΩ next to an insulation reading of 2 GΩ. The gap itself becomes the point of the table.
Fifteen decimal places in one step
One gigaohm is 1,000,000,000 Ω, and one microohm is 0.000001 Ω, so the ratio is 10¹⁵. The formula is GΩ = µΩ × 1e-15. Moving a decimal point fifteen places is not something to do by hand, and a single slip changes the result by a factor of ten or more. For 250 µΩ the answer is 2.5e-13 GΩ, written in full as 0.00000000000025 GΩ. Scientific notation is the only readable choice here. The BIPM SI Brochure defines micro as 10⁻⁶ and giga as 10⁹, and the ohm is the coherent SI unit in between. No constant other than the prefixes is involved, so the factor carries no rounding.
What the default of 10 µΩ produces
The page opens with 10 µΩ and returns 1e-14 GΩ. The raw output may print as 9.999999999999998e-15, which is floating-point display and means 1 × 10⁻¹⁴. Ten microohms is a very low resistance, comparable to a short, well-made bolted copper joint or a heavy bus bar section. On the gigaohm scale, that same value is a decimal point followed by thirteen zeros and a one. The size of the number is a useful reminder that a meter built to read gigaohms has no hope of resolving a contact resistance, and a micro-ohmmeter cannot read an insulation. Each instrument covers a few decades of the scale, not all of them. A test lab that certifies a switchgear panel therefore keeps at least two instruments on the bench, and a report that shows both readings in one unit helps a customer see that each was taken with the right tool.
How far apart are contact and insulation values
A pole with 80 µΩ of contact resistance and 2 GΩ of insulation resistance has a ratio of 80e-6 over 2e9, or 4e-14. In other words, the insulation resists current roughly twenty-five trillion times more than the closed contacts do. That is the property that makes switchgear work, because current takes the contacts and ignores the insulation. If a report lists the contact figure as 8e-14 GΩ and the insulation as 2 GΩ, the order of magnitude is clear at a glance. A reading that moves by a factor of two in the first column, for example from 80 to 160 µΩ, signals a poor contact. A move from 2 to 1 GΩ in the second signals moisture or dirt.
Reading insulation tests in gigaohms
Insulation testers apply a DC voltage, typically 250, 500, 1,000 or 5,000 V, and report the ratio of voltage to leakage current. At 500 V, a reading of 5 GΩ means about 100 nA of leakage, because 500 / 5e9 = 1e-7 A. Moving the other way, 5 GΩ equals 5e15 µΩ, a figure nobody writes in microohms but one that confirms the factor. Acceptance criteria are set by equipment standards and by the owner of the plant, so use the limit from your own procedure rather than a general figure. The conversion helps only when you want to compare a reading with a micro-ohmmeter record in a common unit. Insulation readings also depend on how long the voltage has been applied, since the first seconds include charging current, so note the test duration, often one minute, alongside the value.
Compare cables, windings and bonding in one table
A commissioning file for a motor can hold the winding resistance in milliohms, the bonding path in microohms or milliohms and the insulation in gigaohms. Printing all three in gigaohms is unusual, but the exercise makes a point. A winding of 0.045 Ω is 4.5e-11 GΩ, a bonding link of 300 µΩ is 3e-13 GΩ, and an insulation reading of 20 GΩ is 20 GΩ. Few readers will want all values in one unit permanently, yet when a spreadsheet sorts by value or plots on a log axis, using one unit is the cleanest way to avoid a column of mixed prefixes. Convert once, sort, and keep the original readings in the source column. A log-scale chart then shows the contact values as a cluster near the bottom, the winding values in the middle and the insulation values at the top, with a visible gap between them that no single instrument has to bridge.
Notation habits that prevent errors
Write very small values in scientific notation with the unit attached, such as 2.5e-13 GΩ or 2.5 × 10⁻¹³ GΩ. Avoid long strings of zeros in documents, because the eye cannot count thirteen of them reliably. When you copy the result into a spreadsheet, check that the cell is not formatted to two decimals, which would turn 2.5e-13 into 0.00. Many spreadsheets accept the E notation directly, as in 2.5E-13. Keep the micro sign µ rather than the letter u in formal files, although u is common in plain-text exports. If the source uses uOhm, the page treats it the same way once you enter the number.
Mind the instrument range
The ranges of real instruments set the practical limits. A micro-ohmmeter often has a lowest range of a few thousand microohms with a resolution of 0.1 µΩ, and a megohmmeter may display from kilohms to teraohms. A multimeter can read neither end well. Entering a number into this page does not make it measurable. If your logged value sits outside the instrument range, the display will show an over-range symbol, and any number you copy is not a reading. Use the instrument manual for its accuracy specification, and treat the converter as a unit tool for readings that were actually obtained within range.
Pass or fail stays with the test standard
The converter changes units and nothing more. It does not assess whether a contact or insulation reading passes, it does not correct for temperature or humidity, and it does not convert test voltage and current into resistance. It treats the entered value as a resistance in microohms and reports the same resistance in gigaohms. The factor is a power of ten, so any difference you find against a reference comes from rounding of the entered number. For other prefixes, such as kiloohms, megaohms or teraohms, use the sibling converters, and keep the original reading in your records.