Ventilation in L/s meets fans in CFM

Building ventilation standards and mechanical drawings in much of the world list airflow in liters per second. American fan catalogs, range hood specs and building codes use cubic feet per minute. A designer who works from a metric requirement and selects an American fan, or an owner who compares a European exhaust fan with a local one, converts constantly. The unit pair also appears on appliance labels and in HVAC commissioning reports. This page turns L/s into CFM in one step, so that the requirement and the product can be compared on the same scale without a calculator.

Deriving 2.11888

One cubic foot is 28.316846592 liters, defined from the international foot of 0.3048 m (NIST SP 811). A flow of 1 L/s moves 60 liters in a minute, and 60 / 28.316846592 = 2.11888 cubic feet in that minute. The formula is ft³/min = L/s × 2.11888000329. A handy approximation is to double the L/s figure and add 6 percent. In the reverse direction, 1 CFM is 0.4719 L/s, so a quick conversion from CFM to L/s halves the number and trims a little. The page uses the full twelve digit factor.

Ten liters per second as bathroom fan airflow

Ten liters per second is 21.188800032893155 CFM. A bathroom fan that moves 10 L/s sits at the low end of what a typical home uses, and a small range hood or a ventilation unit for a studio apartment often handles several times as much. The result is mostly a unit anchor. Each L/s is a little over 2 CFM, and a CFM figure that looks about twice the L/s value is correct to within a few percent. If the output looks three times larger, a minute versus second slip has probably crept in. For a dryer vent, a clothes dryer needs a duct that carries its rated airflow, and a 12 L/s figure, which is 25.4 CFM, would be far too weak, so scale matters when you judge whether a number makes sense for the appliance.

Bathroom exhaust fans

Bathroom fan labels in Canada and Australia list L/s, while American housing codes name CFM. A fan rated at 25 L/s delivers 52.97 CFM, which clears a minimum of 50 CFM written into many local rules for intermittent bathroom exhaust. Fan labels give the flow at zero static pressure. Ducts, elbows and a roof cap lower the real flow, so a fan that passes at 52.97 CFM on paper may fall below the requirement when installed. The Home Ventilating Institute rating, which includes a static pressure, is the more reliable figure where it is listed. Duct length and diameter decide the loss. A fan that is fitted with a 100 mm duct and a long run has far less delivered flow than the same fan with a short 150 mm duct. A damper that sticks half shut can cost more flow than the whole duct, so check the damper too when a new fan seems weak.

Kitchen range hoods

Range hood catalogs list the maximum airflow in CFM in the United States and in m³/h or L/s elsewhere. A hood rated at 50 L/s equals 105.94 CFM, a modest figure for a domestic cooktop. Powerful hoods run at several hundred CFM, and building codes in many places require make-up air once the exhaust passes a threshold. The converted number lets you compare a European hood with the airflow limit in your local code. Quiet operation depends on duct size as well, so check the duct diameter the maker recommends. Noise ratings come in sones, and a fan can be loud at the top of its range even when the airflow suits the cooktop. Many cooks run a hood at a lower setting for ordinary frying, so a 50 L/s unit that is quiet at 30 L/s serves well, and the converted 63.6 CFM gives the number for that setting.

Fresh air per person

Ventilation guidance states a fresh air rate per occupant. ASHRAE Standard 62.1 includes a rate of 5 CFM per person for office spaces, a figure often quoted alongside an area rate. In metric terms that is 2.36 L/s per person. An office with 20 occupants needs 100 CFM for the people portion, which equals 47.2 L/s. Confirm the current edition and the occupancy category when you design a real system, since the standard has several rates and the local code may adopt a different one. The conversion keeps both sides of a specification comparable. A classroom for 30 people at 5 CFM each needs 150 CFM, which is 70.8 L/s, for the people share alone, and the rate for the floor area is added on top. Because occupancy varies through the day, controls that track carbon dioxide can lower the airflow when the room is half empty, and the converted values apply at each setting.

Electronics cabinets and PC fans

Computer case fans are rated in CFM, while some industrial enclosure fans list L/s or m³/h. A fan listed at 60 CFM equals 28.3 L/s. A small cabinet fan at 7.5 L/s delivers 15.89 CFM. Airflow ratings are free-air values at zero resistance. Filters, grills and dense components reduce delivery noticeably, so a fan sized exactly to the heat load on paper may be marginal in practice. Compare two fans at the same static pressure if the data sheet shows a curve, and use the conversion for the headline numbers only. In a network cabinet or an equipment rack, the needed airflow follows from the heat to remove and the allowed air temperature rise, which the equipment maker states. Convert the fan rating, and then check it against that requirement with a margin for dust on filters.

Where CFM and L/s get confused

The usual errors involve the time unit. A flow in L/min put in this page as L/s overstates the CFM by a factor of 60. Another slip is mixing CFM with m³/h, where 1 CFM is 1.699 m³/h. Always read the unit next to the number. SCFM and CFM are not identical either, since SCFM refers to standard conditions, but for room ventilation at ordinary conditions the difference is small. The result is rounded for display, and the factor is stored with twelve significant digits.

Ventilation codes and air density

The page converts volume flow and carries no information about static pressure, duct losses, air density at altitude or humidity. A fan moves a fixed volume at a given speed, so the mass of air delivered changes with density, which matters at high elevations. Ventilation requirements in a code are legal numbers, and a converted figure must be compared with the code text and not with a rounded rule of thumb. Use the page for unit translation and rely on a qualified designer for system sizing.