Ventilation drawings in L/s

Building services engineers in Canada, Australia, New Zealand, the United Kingdom and much of Europe write airflow in liters per second on ventilation schedules, extract fan lists and commissioning sheets. US-made fans, hoods and diffusers arrive with CFM labels. A designer matching a catalog item to a specification, or a contractor checking a bill of materials, converts between the two. This page performs that step. A liter per second is a convenient size for room-level airflows, since typical figures run from a few liters per second for a small bathroom exhaust to hundreds for a large kitchen hood. Metric ductwork is often sized in the same unit, so a duct chart that plots pressure loss against flow in L/s lets a designer read the loss for the converted flow directly. Using one unit from the fan schedule through to the duct chart avoids repeated conversions, each of which is a chance for a transcription error.

Factor derivation

A cubic foot holds 28.316846592 liters, derived from the exact foot of 0.3048 m. One minute equals 60 seconds. One CFM therefore equals 28.316846592 / 60 = 0.4719474432 L/s, and the page uses L/s = ft³/min × 0.4719474432. The reverse is ft³/min = L/s × 2.1188800033. These numbers are exact consequences of the definitions in NIST SP 811 and the BIPM SI Brochure. A useful approximation is that one liter per second is about 2.12 CFM, and one CFM is about 0.472 L/s. Because the factor sits just under one half, a CFM figure divided by two is a rough guide to liters per second. The estimate degrades slowly at large flows: 400 CFM halved gives 200 L/s, while the exact figure is 188.8 L/s, a gap of about six percent that matters when you are checking a code minimum.

Default and sample entries

The default of 10 CFM gives 4.7195 L/s. A 1 CFM flow is 0.4719 L/s, 100 CFM is 47.1947 L/s and 250 CFM is 117.9869 L/s. In the other direction, 0.5 L/s is 1.0594 CFM, 5 L/s is 10.5944 CFM, 12 L/s is 25.4266 CFM and 50 L/s is 105.9440 CFM. These sample figures are illustrative and not tied to a code requirement. A habit that helps is to double the L/s value to estimate CFM, then check the exact page result against that estimate. Keep the estimate for sanity checks only, and use the exact factor for anything that goes into a schedule or a specification. The two should agree within about six percent.

Per-person and per-area ventilation rates

Ventilation standards often state outdoor air requirements per person or per floor area. ASHRAE Standard 62.1 gives its rates in both CFM and L/s units, and national codes in metric countries give L/s. An office with 20 occupants at a rate of 5 L/s per person needs 100 L/s, which is 211.89 CFM. A reader comparing a US design with a metric code can use the page for such a rate. The requirement itself belongs to the code that applies to the project, and the page states no rate of its own. For a lobby that needs 6 L/s per person at a design occupancy of 15, the requirement is 90 L/s, or about 190.7 CFM, which sets the minimum size of a supply fan in either system of units. Supply and exhaust figures are often balanced, so converting both with the same factor keeps the difference between them correct, even if each is rounded for the drawing.

Kitchen hoods and exhaust fans

Kitchen extract and bathroom fans make a natural example. A 250 CFM range hood extracts about 118 L/s, and a 50 CFM bathroom fan about 23.6 L/s. Whether either is adequate for the room depends on room size, duct length, makeup air and local rules. Free-air ratings overstate the flow once a duct and hood are attached, because static pressure reduces fan delivery. For that reason, product literature gives a fan curve or rated flow at a stated pressure, and the converted figure should come from the rating at the operating point. Reading a fan curve means finding the pressure the duct system will impose, then reading the flow at that pressure, and only then converting it.

Mistakes with seconds and minutes

A frequent mistake is treating L/s and L/min as interchangeable. A flow of 4.72 L/s is 283.2 L/min, a factor of 60 different, and quoting one when the other is meant leads to a very wrong fan. Another is mixing up CFM, which is cubic feet per minute, with cfs, cubic feet per second. A result in L/s that exceeds the CFM number is a hint that the menus are the wrong way round, since a CFM is worth less than half a liter per second.

Relating to air changes and room size

To estimate air changes per hour, convert L/s to liters per hour by multiplying by 3,600, then divide by the room volume in liters. A flow of 47.19 L/s through a room of 60 m³ holds 169,900 liters an hour against 60,000 liters of volume, about 2.8 changes per hour. The page gives only the first number, and the rest is arithmetic you can do separately. The same logic applies to balancing a room: supply and extract flows in L/s should be converted with identical factors so that the difference between them is unaffected by rounding. Whether 2.8 changes per hour is adequate depends on the use of the room and the applicable standard.

Rounding airflow for ventilation schedules

On ventilation schedules, airflows are usually rounded to whole liters per second or to the nearest 5. A 250 CFM item becomes 118 L/s in a schedule, even though the page shows 117.9869. The unrounded value is better for calculation. When both unit systems appear on a document, put the unit of the governing system first and give the other in parentheses, so a reader knows which figure controls. If an equipment submittal lists 200 CFM and the schedule requires 95 L/s, the converted value of 94.4 L/s falls short by 0.6 L/s, a case where rounding to a whole number would hide the shortfall and a short note on the tolerance is needed.

Fan sizing and ventilation codes excluded

The page changes the unit of an airflow figure. It does not size a fan, check a ventilation standard, estimate duct losses or confirm indoor air quality. Those depend on the building, the climate and the standard in force. Use the converted number as input and consult the manufacturer curve and the applicable code for requirements.