Sensor signals on two scales
Small sensors produce small voltages, and manufacturers state them on whichever scale gives readable numbers. A thermocouple table lists millivolts, while the same part's sensitivity is given in microvolts per degree. An op-amp datasheet gives offset voltage in microvolts and an input signal range in millivolts. A microphone preamp, an ECG front end and a strain gauge bridge each mix both. This page multiplies the millivolt value by 1,000 and shows microvolts, so a signal in one unit can be checked against a limit in the other. People who use it include electronics hobbyists reading datasheets, students in instrumentation labs, and technicians matching a multimeter reading to a sensor specification.
Why the factor is exactly 1,000
The prefix milli is 10^-3 and micro is 10^-6, so one millivolt equals 1,000 microvolts. The volt is defined in the BIPM SI Brochure as one joule per coulomb, and the prefixes are fixed by definition, so there is no uncertainty. Mentally, move the decimal point three places to the right. A reading of 2.5 mV is 2,500 µV, and 0.041 mV is 41 µV. The microvolt symbol uses the Greek letter mu, written µV, and plain text often uses uV, which means the same unit. If the converted number is smaller than the input, the direction is reversed.
Ten millivolts in microvolts
The default of 10 mV gives 10,000 µV. A smaller input of 0.5 mV gives 500 µV, and 150 µV in the other direction equals 0.15 mV. A larger one of 1 V, which is 1,000 mV, is 1,000,000 µV. Check the digit count: moving from milli to micro adds three digits to the integer part. A result with fewer digits than the input points to a unit selected the wrong way around. In a log file that mixes units, it helps to put the value, the unit and the sensor name in separate columns, so that a conversion can be audited without reading the whole row.
Thermocouples and microvolt sensitivity
A type K thermocouple produces about 41 µV per degree Celsius near room temperature, and its output at 100 °C, with the reference junction at 0 °C, is 4.096 mV, or 4,096 µV according to the NIST ITS-90 tables. A meter that reads 4.096 mV is therefore 4,096 µV. A change of one degree changes the output by about 0.041 mV. A data logger with a resolution of 1 µV would resolve about a fortieth of a degree in the best case, before noise, reference junction error and wire effects are included. Compare the sensor and the logger on the same scale before assuming that the readout can show the change you want.
Biosignals in millivolts and microvolts
An ECG signal at the skin is on the order of 1 mV, which is 1,000 µV, and an EEG signal is smaller, around 10 to 100 µV, or 0.01 to 0.1 mV. These magnitudes are typical values from textbooks and vary by electrode position and subject. They explain why EEG amplifiers need higher gain and better noise performance than ECG amplifiers. A datasheet that lists input-referred noise of 2 µV peak to peak is 0.002 mV, which is 0.2 percent of a 1 mV ECG signal but 4 percent of a 50 µV EEG signal. Seeing both numbers in one unit makes the difference between the two applications clear.
Offset and noise figures in datasheets
Precision op amps list input offset voltage in microvolts, for example 25 µV, which is 0.025 mV. If a circuit amplifies by 1,000, that offset becomes 25,000 µV at the output, which is 25 mV. Converting the figure to millivolts helps compare with a signal of, say, 10 mV at the output. The page makes these steps quick. Note that datasheets give a typical and a maximum value, and the maximum is the one to design with. Offset also drifts with temperature, often a few microvolts per degree Celsius, so the number at 25 °C is only part of the picture. For a drift of 0.5 µV per degree and a temperature swing of 40 °C, the extra offset is 20 µV, or 0.02 mV, nearly as large as the room-temperature figure. Add such terms in one unit before comparing them with the smallest signal you need to resolve.
Converting microvolts back to millivolts
To convert in the other direction, select microvolts as the source and millivolts as the target. A value of 50 µV equals 0.05 mV, 150 µV equals 0.15 mV, and 4,096 µV equals 4.096 mV. The page divides by 1,000. Nanovolt and picovolt options are also on the menu for ultra-low signals. A common error when reading a datasheet, a frequent one in quick comparisons, is to confuse µV with mV in a noise specification, which changes the result by a factor of 1,000. Compare the stated noise with the signal in the same unit before judging whether the design has enough margin.
Meter ranges and readings
A multimeter on a 200 mV range often resolves 0.1 mV, which is 100 µV. A reading of 4.1 mV on that range may hide the third decimal, so a signal of 4,096 µV and one of 4,140 µV can look the same. For microvolt-level work, a meter with a dedicated microvolt resolution or a nanovoltmeter is needed. Record the range and resolution along with the value. The conversion keeps the digits you give it, so a result of 4,100 µV from a 4.1 mV reading means a precision of two digits, not four, and should be written with that in mind. The same reasoning applies to a conversion in the other direction: 2,300 µV from a three-digit meter is 2.3 mV, and writing 2.300 mV would add a digit that the display never had.
Scope of the page
The page converts a voltage between two prefixes. It does not interpret a sensor signal, calibrate a thermocouple, compensate for a cold junction, compute amplifier gain or judge noise performance. For those tasks use the sensor tables, the datasheets and the calibration of your instrument. Keep in mind that microvolt-level readings are sensitive to wiring, so a result that looks wrong may come from a loose clip lead or a warm hand on a junction, not from the conversion.