SI property tables and US HVAC worksheets

Material property tables from international sources list specific heat in kJ/(kg·K), while US air-conditioning, boiler and process worksheets run on BTU, pounds and degrees Fahrenheit. A designer who takes a value from a handbook and drops it into a load calculation in the other system has to convert it first. This page does that for specific heat capacity, the energy needed to warm one unit of mass by one degree. It does not apply to the heat capacity of a whole tank or slab, which has its own converter, and it does not apply to volumetric heat capacity, where the denominator is a volume. Enter the SI value, read the US value, and use it in the same equation as before.

Where 0.2388459 comes from

Three exact definitions fix the factor. The BTU (IT) is 1,055.05585262 J, the pound is 0.45359237 kg and the Fahrenheit degree, as an interval, is 5/9 of a kelvin. Dividing the energy by the mass and the temperature interval gives 1 BTU/(lb·°F) = 4,186.8 J/(kg·K) = 4.1868 kJ/(kg·K), which agrees with the table in NIST SP 811. The page uses the inverse, 0.2388459, so 4.1868 kJ/(kg·K) returns 1.0000 BTU/(lb·°F). The same number is also the value of the International Table calorie per gram per kelvin, because the IT calorie is defined as 4.1868 J.

What the default of 10 returns

The default 10 kJ/(kg·K) becomes about 2.3885 BTU/(lb·°F). No ordinary solid or liquid has a specific heat that high, since water, which is unusually high, is close to 4.18 kJ/(kg·K), and some gases such as hydrogen go above 14 kJ/(kg·K). The default is therefore a test value for checking the multiplier and not a real material. If you want a realistic sense of scale, enter 4.18 and 0.9, and compare the outputs, 0.998 and 0.215, with the values you expect from your trade handbook. A very small or very large result for a real material usually points to a wrong prefix or to a kJ/kg versus kJ/(kg·K) mix-up.

Water sits near one BTU per pound and degree

The BTU was originally defined around warming a pound of water by one degree Fahrenheit, and that heritage shows. Liquid water near room temperature has a specific heat of about 4.18 kJ/(kg·K), which converts to 0.9984 BTU/(lb·°F). The exact IT value of 4.1868 gives 1.0000 and sits very close to the water figure. This is the reason hydronic heating rules of thumb treat a pound of water as one BTU per degree, and why the common formula for water-loop heat transfer in BTU per hour uses a constant of 500 for flow in gallons per minute and temperature difference in degrees Fahrenheit. Check any chart against the converted value for water to confirm it uses the same units.

Air in ductwork: 1.005 kJ/(kg·K)

Dry air near room temperature has a specific heat at constant pressure of about 1.005 kJ/(kg·K). Entering 1.005 on this page returns 0.24004 BTU/(lb·°F), the 0.24 figure used throughout US HVAC practice. Multiply it by a standard air density of 0.075 lb/ft³ and by 60 minutes per hour and you get 1.08, the factor in the familiar sensible-heat equation, Q in BTU per hour = 1.08 × cfm × temperature change in °F. A designer who has an SI property table can verify the constant from first principles with this page, and it is a good test of the conversion because the answer is a number every US technician recognizes.

Metals and building materials

Handbooks list the specific heat of aluminum near 0.90 kJ/(kg·K), and this page converts it to about 0.215 BTU/(lb·°F), matching the value many US tables give for aluminum. Copper and steel have lower specific heats than aluminum and fall near 0.385 and 0.49 kJ/(kg·K) in common tables, which convert to about 0.092 and 0.117. The ordering matters in practice: pound for pound, aluminum stores more heat per degree than copper does. These handbook figures are approximate and depend on temperature and alloy, so use the value your project specification names, and use the page for the unit change. For a 100 lb aluminum casting, the heat per degree is 100 × 0.215 = 21.5 BTU/°F, so warming it by 50 °F takes about 1,075 BTU, a figure a shop can compare with the output of its oven.

A temperature interval carries no offset

The denominator of this unit is a degree of temperature difference. A Fahrenheit degree equals 5/9 K, and that fraction is already built into the factor. The 32 that appears when converting a temperature reading from °F to °C never enters here, and neither does 273.15. A common mistake is to convert the specific heat as if the denominator were a thermometer reading, which gives a result that is wrong by a large and temperature-dependent amount. The assumption note on the page makes the same warning, and the fixed factor is the way to avoid that error entirely.

Reverse conversions from US tables

To convert a US value to SI, set From to BTU (IT) per pound per degree Fahrenheit and To to kilojoules per kilogram per kelvin. The familiar 0.24 for air returns 1.0048 kJ/(kg·K), and 1.00 for water returns 4.1868. If a US source gives 0.11 for iron, the SI value is 0.46 kJ/(kg·K). Because the factor is defined, the only uncertainty in the converted number is the one in the original table. A mass in pounds multiplies the BTU form directly to give BTU per degree, while a mass in kilograms multiplies the SI form to give kJ per kelvin.

Limits of this converter

The page converts the unit of a property you already know. It does not select a specific heat for you, and it does not allow for the dependence of specific heat on temperature and pressure, which is large for gases and for materials near a phase change. It also keeps the International Table BTU, so equipment data that use a thermochemical BTU differ by a small fraction of a percent. State the property source and its temperature in your calculation sheet beside the converted value.