The wire table unit

Cable and wire tables written for electricians and technicians often list resistivity as ohm square millimeters per meter, because it fits the way wire is sold: length in meters and cross-section in square millimeters. A handbook for semiconductors or electrochemistry lists the same property in ohm centimeters. This page multiplies Ω·cm by 10,000 and returns Ω·mm²/m. It is useful when a figure from one document has to be inserted into a wire calculation from another, and it saves the work of tracking a factor that mixes a length conversion with an area conversion. Product data sheets from cable makers list conductor resistance directly in Ω/km, and that figure already includes the cross-section, so it is a different quantity from the resistivity you convert here.

How the factor arises

One square millimeter is 10^-6 m², so one Ω·mm²/m equals 10^-6 Ω·m, which is 10^-4 Ω·cm because a meter is 100 centimeters. So Ω·mm²/m = Ω·cm × 10,000. The SI Brochure from the BIPM defines the ohm and the meter, and the factor involves no measured constant. By hand, the decimal point moves four places to the right: 3 Ω·cm is 30,000 Ω·mm²/m. The numerical value of a resistivity in Ω·mm²/m is the same as in µΩ·m, which is why the two units appear side by side in catalogs. When the output is smaller than the input, the menus have been swapped, since a wire-table figure in Ω·mm²/m is 10,000 times the Ω·cm figure for the same metal.

Ten ohm centimeters is 100,000 Ω·mm²/m

The default of 10 Ω·cm returns 100,000 Ω·mm²/m, shown by the engine as 100000.00000000001 because of floating-point rounding. The trailing digit means nothing. A resistivity like this belongs to a poor conductor, since copper is about 0.0168 Ω·mm²/m. The default shows the size of the factor and is not a wire value. For practical wire work the figures to expect are between 0.01 and about 1.5. If you see a result in the thousands for a metal, the input was probably in the wrong unit. Check whether the original figure was in Ω·cm or in µΩ·cm before using it.

A resistance calculation with copper

In wire tables the resistance in ohms is the resistivity in Ω·mm²/m times the length in meters divided by the cross-section in mm². Copper at 1.68 × 10^-6 Ω·cm converts to 0.0168 Ω·mm²/m on the page. For 50 m of wire with a 2.5 mm² cross-section the resistance is 0.0168 × 50 / 2.5 = 0.336 Ω. Electricians often use 0.0175 Ω·mm²/m, a slightly higher practical figure, which is 0.00000175 Ω·cm. The multiplication and division are performed outside the page. Resistance rises with temperature, so a hot cable has a higher value than the 20 degree handbook figure. For a longer run of 120 m with the same cross-section the resistance is 0.0168 × 120 / 2.5 = 0.8064 Ω, and a 4 mm² cable of the same length gives 0.504 Ω. Both figures are for the conductor alone and leave out contact resistance at the terminals.

Aluminum and alloys

Aluminum conductors have a resistivity near 0.0265 Ω·mm²/m, which is 0.00000265 Ω·cm, and the page returns 0.0265 when you enter 0.00000265 Ω·cm. The higher value compared with copper is the reason that an aluminum conductor needs a larger cross-section for the same resistance. Resistance alloys are higher still: nichrome is about 1.1 Ω·mm²/m, or 0.00011 Ω·cm in the reverse direction. Values depend on grade and treatment, so use the data sheet of your wire. The converter helps you put numbers from different sources into one unit, which is the first step in comparing materials. Because the figure for aluminum is about 58 percent higher than copper, an aluminum conductor needs roughly 1.6 times the cross-section of a copper one to match the resistance, before other considerations such as weight and terminations.

Going back to ohm centimeters

Choose Ω·mm²/m as the source and Ω·cm as the target when a wire table value must go into a document that uses Ω·cm. A value of 0.0175 Ω·mm²/m is 0.00000175 Ω·cm, and 1.1 Ω·mm²/m is 0.00011 Ω·cm. Reading a wire table back into Ω·cm means dividing by 10,000, a four-place shift to the left. Since the results are small, use scientific notation in reports: 1.75 × 10^-6 Ω·cm. There are separate pages for conversions to and from Ω·m, so pick the one that matches your pair of units, and check the symbols before you copy a number.

Reading the unit correctly

The unit looks like a ratio, but it is a product: ohms times square millimeters divided by meters. It is the resistance in ohms of a conductor that is one meter long with a cross-section of one square millimeter. That gives a direct reading of the number in the wire context, as ohms for a wire of unit size. In the SI base form the same quantity is in ohm meters, with a factor of 10^-6. When a table lists Ω·mm²/m, do not read the mm² as a separate multiplication of the input. The page treats the entire expression as one unit, and the factor follows from its definition. A quick check of the idea: a 1 m length of wire with a cross-section of 1 mm² and a resistivity of 0.0168 Ω·mm²/m has a resistance of 0.0168 Ω.

Frequent mistakes

Mixing Ω·mm²/m with Ω/m is a common slip. The first is a material property and the second is the resistance of a given wire per meter. Another is entering a value in µΩ·cm and calling it Ω·cm, which changes the result by a million. Copper in Ω·cm is about 0.00000168, and typing 1.68 for it gives a nonsensical answer. Check the order of magnitude: a metal in Ω·mm²/m should be near 0.02 to 1.5. If your result lies far outside that, review the input unit. A single check against a known material saves a lot of rework.

Cable sizing and voltage drop stay with the electrician

Handbook tables list resistivity in Ω·cm and wire tables list it in Ω·mm²/m, so the conversion lets you compare the two. Choosing a cable is a separate job. It needs the current, the run length, the insulation type, the installation method and the rules that apply where the work is done, plus a voltage-drop check and any temperature correction. A qualified electrician or engineer should handle those steps. After conversion, a handbook value in Ω·cm and a wire-table value in Ω·mm²/m sit on the same scale, and that is all the page promises.