US fan ratings meeting metric ventilation codes
An imported fan listed at 350 CFM and a European project specification written in m³/h are the typical pair here. HVAC engineers, installers buying equipment across markets, and building-services students need to match airflow in cubic feet per minute against cubic meters per hour. Airflow per hour is also the unit behind air change rates, since an air change rate is the hourly airflow divided by room volume in the same volume unit. Most European standards and manufacturers list m³/h, while American products use CFM, so a single conversion decides whether a part is large enough. This page applies the factor and can reverse it for metric figures.
How the factor 1.69901079552 arises
One international foot is exactly 0.3048 m, so one cubic foot is exactly 0.3048³ = 0.028316846592 m³. A minute is one sixtieth of an hour, so a flow of 1 ft³/min is 60 ft³/h. Multiplying 60 by 0.028316846592 gives 1.69901079552 m³/h. The page uses m³/h = ft³/min × 1.69901079552, which is exact. The inverse is 0.5885777787 ft³/min per m³/h. NIST SP 811 lists the foot definition. The quick rule that one CFM is about 1.7 m³/h is accurate to within 0.06 percent, which is enough for a rough comparison, though the page gives the precise value. Over a large flow the difference matters: 2,000 CFM by the rule is 3,400 m³/h, while the exact factor gives 3,398.02 m³/h.
Default and typical fan figures
The default 10 CFM becomes 16.9901 m³/h. That is the scale of a small computer or cabinet fan. Larger figures appear in building systems. A 60 CFM entry gives 101.9406 m³/h, 150 CFM gives 254.8516 m³/h, 350 CFM gives 594.6538 m³/h and 1,200 CFM gives 2,038.8130 m³/h. These sample values are illustrative and not tied to a particular product. Scale the numbers with the factor and a small calculator is enough to check them. If you convert a metric rating, 500 m³/h is 294.2889 CFM and 2,000 m³/h is 1,177.1556 CFM. The metric entries show why the reverse factor is useful: ventilation drawings from Europe often list ducts and fans in m³/h, and the US contractor wants CFM for ordering.
From airflow to air changes per hour
The metric unit makes air changes simple. Divide the hourly flow by the room volume in cubic meters. A fan delivering 254.85 m³/h in a 40 m³ room produces about 6.4 air changes per hour. In US units the same room is about 1,413 ft³, and 150 CFM gives 9,000 ft³/h, or 6.4 changes, so both routes agree. Codes set minimum air changes or minimum flow per person or area, and those requirements vary by jurisdiction and use, so the page does not state any limit. Check the code that applies to your project. Air changes are also a simple way to compare two fans of different units, because the room volume cancels once both flows use the same volume unit.
Standard air and real air
Airflow ratings assume particular conditions. In the US, a CFM figure usually refers to air at standard density or at test conditions with a stated static pressure. Fans lose flow as duct resistance rises, so a 350 CFM rating may drop in a long duct with bends. A metric rating in m³/h generally follows the same logic. This conversion changes the unit only and keeps the rating conditions the same. It does not compensate for altitude, temperature, duct losses or filter loading, which is why the manufacturer fan curve remains the reference for design. At high altitude, thinner air carries less mass per unit volume, so a fan moves the same volume but cools or ventilates slightly less than the sea-level rating suggests.
Common ways the number goes wrong
One error is using 1.7 in one direction and 0.59 in the other without checking that they are reciprocals. Another is mixing up CFM with CMH, an informal abbreviation for cubic meters per hour that appears on some data sheets. A third is reading m³/s from a hydraulic table as m³/h and being off by 3,600. Lastly, some data sheets give airflow in L/s and the assumption that 1 CFM equals 1 L/s is wrong, because one CFM is 0.4719 L/s. A quick estimate by hand protects against all of these. Multiplying by 1.7 and checking that the answer has the expected number of digits takes seconds and catches most slips.
Rounding and reporting the result
Fan ratings are typically given to two or three significant figures, so a conversion of 350 CFM is fairly reported as 595 m³/h, not 594.653778432 m³/h. Rounding to the nearest whole cubic meter per hour is common on product sheets, and rounding to the nearest 5 or 10 is common on specifications. The reverse direction deserves the same care: 500 m³/h is 294.29 CFM, which a US specification might state as 295 CFM or simply 300 CFM for ordering. Keep the unrounded value in calculations so repeated rounding does not accumulate, and round only when you present the final figure. A cleanroom or laboratory exhaust specified in m³/h converts the same way, but those spaces carry their own standards for air change rates and pressure relationships, which are outside this page.
Airflow conversion without fan sizing
The page converts a flow figure and nothing else. It does not size a fan, check ventilation compliance, estimate duct pressure drop or evaluate indoor air quality. Nor does it say whether a unit is oversized, which affects noise and energy use as well as airflow. Those tasks depend on room volume, occupancy, duct layout and the standards in force where the building stands. Use the converted figure as an input to your design method and rely on the manufacturer data and the applicable code for requirements.