Finding conductivity from a measured heat flow
Thermal conductivity describes how readily a material passes heat by conduction. If you can measure how much heat flows through a flat layer of known size while its two faces are held at different temperatures, you can work the property out directly. This page does that arithmetic. You enter the heat flow rate in watts, the layer thickness in meters, the face area in square meters and the temperature difference across the layer in kelvin. The result is conductivity in watts per meter per kelvin, written W/(m·K). The situation behind it might be a guarded hot plate test, a wall section in a test chamber or a homemade experiment with a small heater and a slab of foam. The same relationship also works in the other direction. Once you have a conductivity from a data sheet, it tells you how much heat a wall or panel will leak. The page covers only the idealized case in its assumptions.
Fourier's law and the default numbers
The relationship is Fourier's law of conduction for a slab: Q = k × A × ΔT / L, where Q is the heat flow rate, k the conductivity, A the area, ΔT the temperature difference and L the thickness. Solving for k gives the formula the page uses: k = Q × L / (A × ΔT). With the default inputs, 20 W flows through a layer 0.1 m thick and 2 m² in area while the two faces differ by 10 K. The numerator is 20 × 0.1, which is 2. The denominator is 2 × 10, which is 20. Dividing gives 0.1 W/(m·K), a value in the range of dry softwood, which is roughly 0.1 to 0.15. OpenStax College Physics presents the same relationship in its section on conduction, with heat transfer proportional to area and temperature difference and inversely proportional to thickness. Because the formula is a product and a quotient, every input scales the answer in a predictable way. Doubling the thickness doubles k, and doubling the area halves it.
Temperature difference in kelvin or degrees Celsius
The input is the magnitude of the temperature difference, so you enter a positive number whichever face is hotter. A difference of 10 K is the same size as a difference of 10 °C, because the kelvin and the Celsius degree are the same size. You can therefore subtract two Celsius readings and enter the result directly. Fahrenheit needs care: a difference of 18 °F equals only 10 K, since one Fahrenheit degree is 5/9 of a kelvin. Do not enter an absolute temperature such as 293 K as the difference. The field wants the gap between the two faces of the layer, not the temperature of either one. A difference of zero cannot be used, because the formula divides by it and the calculator requires a finite result. A zero difference also means no net heat flow, so there would be nothing to measure. Larger differences give a more readable signal, although they also shift the average temperature of the sample, and conductivity itself changes slightly with temperature.
Where each input comes from
Heat flow rate usually comes from electrical power. A resistive heater of known voltage and current delivers V × I watts, and if all of that passes through the sample, it is Q. A heat flux sensor between the layers is the other common source. Thickness is measured with calipers or a micrometer at several points, and the average is used, since foam boards and wall materials are rarely perfectly uniform. Area is the face through which heat flows, not the total surface of the sample. A square test panel 0.5 m on a side has a face area of 0.25 m². Temperature difference comes from thermocouples or thermistors fixed to each face with good thermal contact. A thermocouple that floats in the air near the surface reads a blend of surface and air temperature and will understate the difference across the layer. Keep every input in the units shown on the page: watts, meters, square meters and kelvin. A thickness of 10 cm must be entered as 0.1.
A second example with an insulation batt
Suppose a test setup passes 12 W through a mineral wool batt 0.09 m thick with a face area of 1.5 m², and the two faces settle 20 K apart. The numerator is 12 × 0.09, or 1.08. The denominator is 1.5 × 20, or 30. The conductivity is 1.08 / 30, which is 0.036 W/(m·K). That sits inside the range usually quoted for mineral wool and fiberglass, which is about 0.03 to 0.045, so the measurement looks plausible. The numbers are illustrative and do not describe a particular product. From this value you can find the thermal resistance of the layer, which is the thickness divided by the conductivity: 0.09 / 0.036 = 2.5 m²·K/W. Multiplying by 5.678 converts that to the US R-value unit, ft²·°F·h/Btu, giving about 14.2. A result near the expected range for the product type is a good sign that the units and measurements are consistent.
Typical magnitudes for a sanity check
Knowing the usual range for common materials is the fastest way to catch a mistake. Still air at room temperature conducts about 0.026 W/(m·K), and rigid foam boards fall near 0.02 to 0.04 because they trap gas in small cells. Mineral wool and fiberglass sit around 0.03 to 0.045. Dry softwood is roughly 0.1 to 0.15, and gypsum board is a bit higher. Common brick runs from about 0.6 to 1.0, still water is near 0.6, window glass is close to 1.0 and ordinary concrete falls between roughly 1 and 2. Metals are far above everything else: carbon steel is in the tens, aluminum is a couple of hundred, and copper is about 400. If your result for a foam board comes out at 3.6 or 360, a unit slipped. The most common slip is entering a thickness in centimeters, which makes the answer 100 times too large. Entering millimeters makes it 1,000 times too large.
A copper rod and a brick wall
Two more calculations show how different the property can be. First, a copper bar with a cross-section of 4 cm² carries 40 W along a 0.25 m length while its ends differ by 62.5 K. Convert the area first: 4 cm² is 0.0004 m², because one square meter holds 10,000 square centimeters. The numerator is 40 × 0.25 = 10, and the denominator is 0.0004 × 62.5 = 0.025, so k = 400 W/(m·K), the usual figure for copper. Second, a brick wall section 0.2 m thick and 10 m² in area loses 350 W when the inside surface is 10 K warmer than the outside surface. The numerator is 350 × 0.2 = 70, the denominator is 10 × 10 = 100, and the conductivity is 0.7 W/(m·K), typical of clay brick. Notice how the brick, despite its low conductivity, passes hundreds of watts because its area is large. Both examples are illustrative setups, not measurements of specific samples.
From conductivity to R-value and U-factor
Building work rarely quotes conductivity alone. The resistance of a layer is its thickness divided by its conductivity, written R = L / k in SI units of m²·K/W, and the U-factor is the reciprocal, 1 / R. Layers in series add their resistances, so a wall made of gypsum board, insulation and cladding has a total R equal to the sum of the parts, plus the surface air films. US R-values use ft²·°F·h/Btu, and one SI unit equals 5.678 US units. Conductivity in US practice is often given in Btu·in/(h·ft²·°F), and 1 W/(m·K) equals about 6.933 of those. Applying that to the batt above, 0.036 × 6.933 gives about 0.25, so the batt provides roughly R-4 per inch, since R per inch is the reciprocal. These conversions let you compare a measured value from this page with American product labels, which usually list R-values for a stated thickness rather than conductivity.
What the assumptions mean in practice
The model assumes one-dimensional steady conduction through a uniform slab with no surface losses. Steady means the temperatures have stopped drifting, which for a thick, massive sample can take hours. Reading values while the sample is still warming up gives a heat flow that includes energy being stored in the material. One-dimensional means all heat travels straight through the thickness. Real panels also leak heat out of their edges, which is why laboratory hot plate tests use a guard ring around the metered area, and why a small sample with large edge losses overstates the flow. Uniform means the same material throughout, so moisture, compression, joints and layered construction all break the assumption. Porous insulation also moves heat by radiation and by small convection currents inside the pores, so the number you compute is an apparent conductivity for that sample and temperature range. Finally, the temperatures must be taken on the faces of the material, because the thin air films on each side add resistance of their own.
How measurement errors carry through
Because k = Q × L / (A × ΔT), the relative errors of the four inputs combine. Suppose the heat flow is uncertain by 2 percent, the thickness by 3 percent, the area by 2 percent and the temperature difference by 5 percent. Adding them in the worst case gives 12 percent. If the errors are independent, combining them as the square root of the sum of squares gives the square root of 4 + 9 + 4 + 25, which is about 6.5 percent. The temperature difference is usually the weakest link. A difference of 2 K measured to within 0.2 K is already a 10 percent uncertainty, so use a larger difference when the sample allows it. Standardized methods exist for careful work, including ASTM C177 for the guarded hot plate and ASTM C518 and ISO 8301 for heat flow meters. This calculator does the arithmetic, but it does not replace a controlled test or a certified result.